background image

7 Commissioning

Installation manual

13

FBA35~14FBA35~7ADEA35~125A2VEB
Split system air conditioners
4P456962-1D – 2018.08

Setting content:

Then

3

M

C1

C2

Airflow adjustment is OFF

11(21)

7

01

Press ON/OFF to return to normal operating
mode.

Possible consequence: 

The operation lamp

will light up and the unit will start the fan
operation for airflow automatic adjustment.

03

Operation stops after 1 to 8 minutes.

Possible consequence: 

Setting is finished

and the operation lamp will be off.

02

If  there  is  no  change  after  airflow  adjustment,  perform  the  setting
again.

User interface

Check  the  indoor  unit  setting:  the  second  code  number  of  mode
11(21) must be set to 01.

Change  the  second  code  number  according  to  the  external  static
pressure of the duct to be connected as in table below.

External static pressure

3

M

C1

C2

Class

35

50

60

71

100

125

140

13(23)

6

01

30

30

30

30

40

50

50

02

03

30

30

30

30

04

40

40

40

40

40

05

50

50

50

50

50

50

50

06

60

60

60

60

60

60

60

07

70

70

70

70

70

70

70

08

80

80

80

80

80

80

80

09

90

90

90

90

90

90

90

10

100

100

100

100

100

100

100

11

110

110

110

110

110

110

110

12

120

120

120

120

120

120

120

13

130

130

130

130

130

130

130

14

140

140

140

140

140

140

140

15

150

150

150

150

150

150

150

Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

3

M

C1

C2

±2500 h (light)

10(20)

0

01

±1250 h (heavy)

02

No notification

3

02

2 user interfaces:

 When using 2 user interfaces, one must be set

to "MAIN" and the other to "SUB".

7

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

7.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

7.2

To perform a test run

This  task  is  only  applicable  when  using  the  BRC1E52  or  BRC1E53
user  interface.  When  using  any  other  user  interface,  see  the
installation manual or service manual of the user interface.

NOTICE

Do not interrupt the test run.

INFORMATION

Backlight.

  To  perform  an  ON/OFF  action  on  the  user

interface,  the  backlight  does  not  need  to  be  lit.  For  any
other  action,  it  needs  to  be  lit  first.  The  backlight  is  lit  for
±30 seconds when you press a button.

1

Perform introductory steps.

(3)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

Summary of Contents for ADEA100A2VEB

Page 1: ...ish Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB FBA35A2VEB9 FBA50A2VEB9 FBA60A2VEB9 FBA71A2VEB9 ADEA35A2VEB ADEA50A2VEB ADEA60A2VEB ADEA71A2VEB ADEA100A2VEB ADEA125A2VEB ...

Page 2: ...ilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите и...

Page 3: ...ate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka ž...

Page 4: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 5: ... users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the indoor unit Indoor unit installation manual Installation instructions Format Paper in the box o...

Page 6: ...any place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Spacing Mind the following requirements 500 a e d b c f g a Service space b Drain pipe c Power supply wiring port d Transmissio...

Page 7: ...the flange c Fixing screw Ceiling strength Check whether the ceiling is strong enough to support the weight of the unit If there is a risk reinforce the ceiling before installing the unit Installation options a c e b 125 460 160 160 300 375 a c b 460 d d f f 125 300 A B Class f mm 35 50 760 60 71 1060 Class f mm 100 140 1460 A Mounting the air inlet with a canvas connection B Mounting the air inle...

Page 8: ...room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct work The ducting is to be field supplied Air inlet side Attach the duct and intake side flange field supply For connecting the flange use 7 accessory screws a b b ...

Page 9: ... insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f Dr...

Page 10: ...ntly resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation Insul...

Page 11: ...e electrical wiring does NOT obstruct proper reattachment of the service cover It is important to keep the power supply and the transmission wiring separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 12: ...t the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Ensure that equipment is connected only to a supply with a short circuit power Ssc greater than or equal to Ssc in table below Combination FBA35A FBA50A FBA60A FBA71A RZAG71M 2 1 RZQG71L RZAG100M 3 2 31 2 1 30 RZQG100L RZAG125M 4 3 33 3 2 32 2 2 05 RZQG125L RZAG140M 4 3 33 3 ...

Page 13: ...ICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 1 Checklist before commissioning After the installation of the unit first check the following items Once all below checks are fulfilled the unit MUST be closed ONLY then can the unit be powered up You read the complete installation instructions as described in the installer refe...

Page 14: ...door unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor uni...

Page 15: ...ND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES TH...

Page 16: ...4P456962 1D 2018 08 Copyright 2017 Daikin ...

Reviews: