background image

6 Disposal

Installation manual

14

3(A)MXM+3(A)MXF+4MXM+5MXM

R32 Split series

3P600450-1C – 2020.05

A

1
2
3
4
5

SW3

2

1

2

Press  the  wiring  error  check  switch  (SW3)  on  the  outdoor  unit
service PCB.

Result: 

The  service  monitor  LEDs  indicate  whether  correction

is  possible  or  not.  For  details  about  how  to  read  the  LED
display, refer to the service manual.

Result: 

Wiring  errors  will  be  corrected  after  15-20  minutes.  If

automatic correction is not possible, check the indoor unit wiring and
piping in the usual way.

INFORMATION

▪ The number of LEDs displayed depends on the number

of rooms.

▪ The wiring error check function will NOT work if outside

temperature is ≤5°C.

▪ After  wiring  error  check  operation  is  completed,  LED

indication will continue until normal operation starts.

▪ Follow the product diagnosis procedures. For details of

product error diagnosis refer to service manual.

Status of LEDs:

▪ All LEDs flash: automatic correction is NOT possible.

▪ LEDs flash alternately: automatic correction is completed.

▪ One or more LEDs are permanently on: abnormal stop (follow the

diagnosis procedure on the back of the right side plate and refer to
service manual).

5.3.2

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test run operation may be done in cooling or heating

mode.

Prerequisite: 

Test  run  should  be  done  in  accordance  with  the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.

2

Measure the temperature at the indoor unit inlet and outlet after
running the unit for about 20 minutes. The difference should be
more than 8°C (cooling) or 20°C (heating).

3

First  check  operation  of  each  unit  individually,  then  check
simultaneous  operation  of  all  indoor  units.  Check  both  heating
and cooling operation.

4

When test run is finished, set the temperature to a normal level.
In cooling mode: 26~28°C, in heating mode: 20~24°C.

INFORMATION

▪ Test run can be disabled if necessary.

▪ After the unit is turned OFF, it cannot be started again

for 3 minutes.

▪ When the test run is started in the heat mode right after

turning the safety breaker on, in some cases no air will
be  output  for  about  15  minutes  in  order  to  protect  the
unit.

▪ Operate  only  air  conditioner  during  test  run.  Do  NOT

operate  the  Hybrid  for  Multi  or  the  DHW  generator
during test run.

▪ During  cooling  operation,  frost  may  form  on  the  gas

stop valve or other parts. This is normal.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

5.4

Starting up the outdoor unit

See  the  indoor  unit  installation  manual  for  configuration  and
commissioning of the system.

6

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

6.1

To pump down

NOTICE

For  the  Hybrid  for  Multi,  all  required  precautions  must  be
taken to avoid possible freezing damage at the water heat
exchanger  before  this  function  is  allowed  to  be  used  or
activated.  For  detailed  information  see  the  indoor
installation manual.

Example: 

To  protect  the  environment,  pump  down  when  relocating

the unit or when disposing of the unit.

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

  If  you  want  to  pump

down  the  system,  and  there  is  a  leak  in  the  refrigerant
circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the
system  into  the  outdoor  unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor
because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

NOTICE

During pump down operation, stop the compressor before
removing  the  refrigerant  piping.  If  the  compressor  is  still
running and the stop valve is open during pump down, air
will be sucked into the system. Compressor breakdown or
damage to the system can result due to abnormal pressure
in the refrigerant cycle.

Summary of Contents for 4MXM-N9

Page 1: ...ation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3MXM40N2V1B9 3MXM52N2V1B9 3MXM68N2V1B9 4MXM68N2V1B9 4MXM80N2V1B9 5MXM90N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68...

Page 2: ...r Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ioning 13 5 3 Trial operation and testing 13 5 3 1 About wiring error check 13 5 3 2 To perform a test run 14 5 4 Starting up the outdoor unit 14 6 Disposal 14 6 1 To pump down 14 6 2 To start and sto...

Page 5: ...he room in which the appliances are installed operated and stored must be larger than the minimum floor area This applies to Indoor units without refrigerant leakage sensor in case of indoor units wit...

Page 6: ...MXM68 3MXF68 5 5 m2 4MXM68 6 5 m2 4MXM80 9 8 m2 5MXM90 10 4 m2 Shortest allowable length per room is 3 m Outdoor unit Refrigerant piping length to each indoor unit Refrigerant piping total length 3MXM...

Page 7: ...during shipment During installation of the refrigeration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces...

Page 8: ...9 62 75 NOTICE Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Be careful NOT to overtighten the nut or the smaller pipe may be damaged about 2 3 1 t...

Page 9: ...egislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GW...

Page 10: ...ide of the outdoor unit near the gas and liquid stop valves 4 5 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING Appliance shall be installed in accordance with national wiring re...

Page 11: ...door units so that the terminal numbers match Make sure to match the symbols for piping and wiring 3 Make sure to connect correct wiring to correct room e B e E e C e D a A e A a C a D a E a B b c d a...

Page 12: ...r indoor units enter the standby mode Priority during high power operation If the indoor unit on which the priority room function is set operates at high power the other indoor units will run with red...

Page 13: ...signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and...

Page 14: ...ON Test run can be disabled if necessary After the unit is turned OFF it cannot be started again for 3 minutes When the test run is started in the heat mode right after turning the safety breaker on i...

Page 15: ...s the forced cooling operation switch SW1 to begin forced cooling 9 Press the forced cooling operation switch SW1 to stop forced cooling A 1 2 3 4 5 7 SW1 6 1 4 5 NOTICE Take care that while running f...

Page 16: ...gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Re...

Page 17: ...9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e f k a b c g i d r s t v A v B v C...

Page 18: ...uT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT...

Page 19: ...4CuT 6 4CuT 15 9CuT 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r s t v A u A u B u C u D u E v B v C v D v E u d p o o n l m l l w x q h y y 5MXM90 a Heat exchanger h Distributor o A...

Page 20: ...3P600450 1C 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Reviews: