background image

7 Technical data

Installation manual

15

3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
3P600450-1C – 2020.05

Pump down operation will extract all refrigerant from the system into
the outdoor unit.

1

Remove  the  valve  cap  from  the  liquid  stop  valve  and  the  gas
stop valve.

2

Carry  out  forced  cooling.  See 

"6.2  To  start  and  stop  forced

cooling" 

[

4

 15].

3

After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.

4

Check on the manifold if the vacuum is reached.

5

After  2-3  minutes,  close  the  gas  stop  valve  and  stop  forced
cooling.

a

c

b

d

d

e

a

Gas stop valve

b

Closing direction

c

Hexagonal wrench

d

Valve cap

e

Liquid stop valve

6.2

To start and stop forced cooling

1

Turn OFF the power.

2

Remove the service cover and the switch box cover.

3

Remove the service PCB switch cover.

4

Set DIP switch SW5 and SW6 to OFF.

5

Set DIP switch SW2 to COOL.

4

3

2

1

2

1

4

3

2

1

2

1

HEAT

COOL

A

1
2
3
4
5

2

3

SW5

SW6

SW2

OFF

ON

1

6

Reattach  the  service  PCB  switch  cover,  switch  box  cover  and
service cover.

7

Turn ON the outdoor unit.

8

Press the forced cooling operation switch SW1 to begin forced
cooling.

9

Press  the  forced  cooling  operation  switch  SW1  to  stop  forced
cooling.

A

1
2
3
4
5

7

SW1

6

4

5

=

NOTICE

Take  care  that  while  running  forced  cooling  operation,  the
water  temperature  remains  higher  than  5°C  (see
temperature  read  out  of  the  indoor  unit).  You  can  achieve
this, for example, by activating all fans of the fan coil units.

7

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

7.1

Wiring diagram

7.1.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit.  Part  numbering  is  by  Arabic  numbers  in  ascending  order  for
each part and is represented in the overview below by "*" in the part
code.

Symbol

Meaning

Symbol Meaning

Circuit breaker

Protective earth

Connection

Protective earth (screw)

,

Connector

A

Rectifier

Earth

Relay connector

Field wiring

Short-circuit connector

Fuse

Terminal

INDOOR

Indoor unit

Terminal strip

OUTDOOR

Outdoor unit

Wire clamp

Residual current
device

Symbol

Colour

Symbol

Colour

BLK

Black

ORG

Orange

BLU

Blue

PNK

Pink

BRN

Brown

PRP, PPL

Purple

GRN

Green

RED

Red

GRY

Grey

WHT

White

YLW

Yellow

Summary of Contents for 4MXM-N9

Page 1: ...ation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3MXM40N2V1B9 3MXM52N2V1B9 3MXM68N2V1B9 4MXM68N2V1B9 4MXM80N2V1B9 5MXM90N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68...

Page 2: ...r Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ioning 13 5 3 Trial operation and testing 13 5 3 1 About wiring error check 13 5 3 2 To perform a test run 14 5 4 Starting up the outdoor unit 14 6 Disposal 14 6 1 To pump down 14 6 2 To start and sto...

Page 5: ...he room in which the appliances are installed operated and stored must be larger than the minimum floor area This applies to Indoor units without refrigerant leakage sensor in case of indoor units wit...

Page 6: ...MXM68 3MXF68 5 5 m2 4MXM68 6 5 m2 4MXM80 9 8 m2 5MXM90 10 4 m2 Shortest allowable length per room is 3 m Outdoor unit Refrigerant piping length to each indoor unit Refrigerant piping total length 3MXM...

Page 7: ...during shipment During installation of the refrigeration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces...

Page 8: ...9 62 75 NOTICE Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Be careful NOT to overtighten the nut or the smaller pipe may be damaged about 2 3 1 t...

Page 9: ...egislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GW...

Page 10: ...ide of the outdoor unit near the gas and liquid stop valves 4 5 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING Appliance shall be installed in accordance with national wiring re...

Page 11: ...door units so that the terminal numbers match Make sure to match the symbols for piping and wiring 3 Make sure to connect correct wiring to correct room e B e E e C e D a A e A a C a D a E a B b c d a...

Page 12: ...r indoor units enter the standby mode Priority during high power operation If the indoor unit on which the priority room function is set operates at high power the other indoor units will run with red...

Page 13: ...signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and...

Page 14: ...ON Test run can be disabled if necessary After the unit is turned OFF it cannot be started again for 3 minutes When the test run is started in the heat mode right after turning the safety breaker on i...

Page 15: ...s the forced cooling operation switch SW1 to begin forced cooling 9 Press the forced cooling operation switch SW1 to stop forced cooling A 1 2 3 4 5 7 SW1 6 1 4 5 NOTICE Take care that while running f...

Page 16: ...gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Re...

Page 17: ...9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e f k a b c g i d r s t v A v B v C...

Page 18: ...uT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT...

Page 19: ...4CuT 6 4CuT 15 9CuT 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r s t v A u A u B u C u D u E v B v C v D v E u d p o o n l m l l w x q h y y 5MXM90 a Heat exchanger h Distributor o A...

Page 20: ...3P600450 1C 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Reviews: