![background image](http://html.mh-extra.com/html/daikin/4mxl36tvju/4mxl36tvju_service-manual-removal-procedure_501132014.webp)
Thermistor ASSY / Electronic Expansion Valve Coil for Bypass Circuit / Four Way Valve Coil
Si121858E
12
Removal Procedure
4. Thermistor ASSY / Electronic Expansion Valve
Coil for Bypass Circuit / Four Way Valve Coil
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Step
Procedure
Points
1. Remove the connecting
wires and power supply
wire.
To remove the thermistor
ASSY, rear plate has to be
removed. If the conduit
mounting plate can be
unhooked, the rear plate can
be removed without
removing connecting wires.
4-room model does not have
the terminal block for Room
E.
1
Remove the screws on
the terminal blocks,
earth/ground screws
and disconnect the 5
connecting wires
(Room A, B, C, D, E)
and power supply wire.
2
Loosen the lock nuts
and remove conduits
together with the 5
connecting wires
(Room A, B, C, D, E)
and the power supply
wire.
2. Remove the rear plate.
1
Remove the 9 screws.
Power
supply
Room E
Room D
Room C
Room B
Room A
Terminal block
(R25782)
Lock nut
Lock nut
Conduit
Conduit
(R25783)
(R25784)