5
Precautions on Outdoor Unit Installation
Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after
•
installed.
In accordance with the foundation drawing in
fi
x the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10
•
foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.
•
20
Outdoor Unit Installation Guidelines
Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet air
fl
ow, follow the installation guidelines below.
•
For any of the below installation patterns, the wall height on the outlet side should be 1200mm or less.
•
More than 100
Side view
More than 350
1200
or less
Wall facing one side
Walls facing two sides
Top view
More than 50
More
than 100
More than 50
More than 350
unit: mm
Selecting a Location for Installation of
the Indoor Units and Water Heater
The maximum allowable length of refrigerant piping, and the maximum allowable height difference, between the indoor unit or
•
water heater and outdoor unit are listed below. (The shorter the refrigerant piping, the better the performance. Connect so that
the piping is as short as possible.
Shortest allowable length per room is 3m.
)
Piping to each indoor unit
25m max.
∗
Additional refrigerant charging is required if the total
length of the indoor unit connection pipe exceeds 30m.
Refer to charging with refrigerant (page 9) for details.
Total len gth of piping between all indoor units
60m max.
Piping to water heater
15m max.
Indoor unit
Outdoor unit
Water heater
Level
difference:
15m max.
Level
difference:
7.5m max.
Level
difference:
7.5m max.
Level
difference:
15m max.
Outdoor unit
Indoor unit
Level
difference:
7.5m max.
Level
difference:
7.5m max.
Water heater
If the outdoor unit is positioned higher than the indoor units
and water heater.
If the outdoor unit is positioned otherwise.
(If lower than one or more indoor units.)
∗