12
English
Wiring
Electrical wiring connection with indoor unit
1.
WARNING
Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or
fi
re.
•
Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
•
terminal block.) Doing so may cause electric shock or
fi
re.
Be sure to install an earth leak detector. (One that can handle higher harmonics.)
•
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
•
Do not connect the power wire to the indoor unit. Doing so may cause electric shock or
fi
re.
•
Do not turn on the safety breaker until all work is
•
completed.
Strip the insulation from the wire (20mm).
1)
Connect the connection wires between the indoor and
2)
outdoor units so that the terminal numbers match.
Tighten the terminal screws securely. We recommend a
fl
athead screwdriver be used to tighten the screws. The
screws are packed with the terminal board.
Be sure to match the symbols for wiring and piping.
3)
Pull the wire and make sure that it does not disconnect.
4)
Then
fi
x the wire in place with the wire retainer.
Safety
breaker
Earth leakage
circuit breaker
Outdoor unit
50Hz 220-240V
Be sure to use the
dedicated circuits.
To room B
To room C
60245 IEC 57
If the length of a connection wire is
10m or more, use
F
2.0mm wire.
Room A
Room
B
Room
C
Room
A
Indoor unit
<Ground terminal installation>
Use the following method when installing a single core wire.
1)
A single core wire
Flat washer
Screw
Arrow view
Use the following method when installing the round crimp-style terminal.
2)
Arrow view
Flat washer
Screw
Round
crimp-style
terminal
Good
Round crimp-
style terminal
Flat washer
Screw
Wrong
Flat washer
Round crimp-
style terminal
Screw
Shape the wires so that there
is no lifting of the service
hatch or other structural parts.
Use the specified wires and
connect them securely.
Wire
retainer
Be sure to clamp the
wire for power source
on this location.
CAUTION
In case using stranded wires is unavoidable for some reason,
•
make sure to install the round crimp-style terminals on the tip.
Place the round crimp-style terminals on the wires up to the
covered part and secure in place.
Stranded wire
Round crimp-style terminal
When connecting the connection wires to the terminal board
•
using a single core wire, be sure to perform curling.
Problems with the work may cause heat and
fi
res.
NOTE
This air conditioner must be earthed.
•
For earthing, follow the applicable local standard for electrical installations.