Indoor Unit
SiBE121123_A
45
Printed Circuit Board Connector Wiring Diagram
1.9
FFQ25/35/50B8V1B, FFQ25/35/50B9V1B
Control PCB
1) X5A
Connector for terminal board (for wired remote controller)
2) X10A, X11A
Connector for transformer
3) X15A
Connector for float switch
4) X17A, X18A
Connector for indoor heat exchanger thermistor
5) X19A
Connector for room temperature thermistor
6) X20A
Connector for fan motor
7) X24A
Connector for signal receiver PCB
(when the wireless remote controller is used)
8) X25A
Connector for drain pump motor
9) X27A
Connector for terminal board (for inter-unit wiring)
10) X33A
Connector for wiring adaptor PCB (option)
11) X35A
Connector for group control adaptor (option)
12) X36A
Connector for swing motor
13) X40A
Connector for ON/OFF input from outside (option)
14) X60A, X61A
Connector for interface adaptor (option)
15) HAP
LED for service monitor (green)
16) SS1
Selector switch for emergency
X27A
X11A
X33A
X10A
X19A X60A X61A
X5A
X35A
X24A
HAP
X15A
X17A
SS1
X40A
X36A
X18A
X25A
X20A
2P095006-8
2P197080-6