Daikin McQuay 910121754 Installation & Maintenance Data Download Page 8

Page 8 of 16 / IM 1171-3

Setpoint Analog Range Tolerance

Table 3: Setpoint analog range tolerance

Setpoint Analog Tolerance

55° to 95°F Scale

-5° to +5°F Scale

Terminal 3 Analog Output

@ 55

°

F (min.)

@ -5

°

F (min.)

0.0 to 0.10 vdc

@65

°

F

@-2.5

°

F

1.3 to 1.42 vdc

@75

°

F

@0

°

F

2.12 to 2.2 vdc

@85

°

F

@+2.5

°

F

2.58 to 2.63 vdc

@95

°

F (max.)

@+5

°

F (max.)

3.0 to 4.0 vdc

Sensor Error

Sensor Error

Full Scale ≈ 5 vdc

Initial Start-Up Occupied Sequence:

On initial installation power-up, the sensor is in “Occupied” 

mode with a solid occupied icon  and DC voltage at terminal 

“U”. If the “STATUS/DOT” input on Terminal 1 from the 

controller indicates occupied (“ON” continuous), then the 

unit continues to stay “Occupied”. If the “STATUS/DOT” 

input on Terminal 1 from the controller indicates unoccupied 

(5 seconds “ON” then 5.5 seconds “OFF”), then the occupied 

icon will flash the desired occupancy state every 8 seconds, 

indicating to the user a mismatch of the desired occupied 
status and system occupied status at the controller

Power Fail Start-Up Occupied 
Sequence:

On a power failure, the sensor retains its last known desired 

occupancy status in non-volatile memory. On restoration of 

power, the sensor restores its last known desired occupancy 

state from memory. The occupied icon will reflect this with a 

solid (occupied) or hollow (unoccupied)  indication and ter-
minal “U” will have voltage applied (occupied) or grounded 

(unoccupied). If the “STATUS/DOT” input on Terminal 1 

from the controller matches this occupancy state then the oc-
cupied status icon will continue to be solid or hollow depend-

ing on the last known state. If the “STATUS/DOT” input on 

Terminal 1 from the controller is different from the sensor 

occupied state, then the occupied icon will flash the desired 

occupancy state every 8 seconds indicating to the user a 
mismatch of the desired occupied status and system occupied 
status at the controller.

Display Descriptions

Numerical Display

The factory setting default numerical display (

Figure 7

shows current temperature (°F or °C) and toggles to humidity 

and setpoint display every 5 seconds. 

Figure 7: Sensor numerical display

Adjusting The Setpoint (Temperature or 
Humidity)

Whichever is displayed at the time, temperature or humidity:

  Push the 

 or 

 button, the displayed setpoint can 

be adjusted up or down.

•  

After an adjustment, the setpoint is displayed for 5 seconds.

During the setpoint display push 

 (System Mode Button) 

to switch between the temperature display or the humidity 
display.

•  

Push the 

 or 

 button, the displayed setpoint 

can be adjusted up or down. (See 

"Front Panel Button 

Operation" on page 10

 for details.)

The unit can also be programmed in the field to “Setpoint 

Only” display or Setpoint Lockout. See the 

"Optional Techni

-

cian Adjustments"

 on page 11.

Occupied Icon Indicator:

The Occupied Icon on the left side of the display indicates 
whether the room sensor is in the Occupied or Unoccupied 
Mode, (

Figure 8

).

Figure 8: Occupied & unoccupied icons

 = 

Occupied

 

 = 

Unoccupied

Solid is Occupied and Hollow is Unoccupied. 

•  

A blinking icon every 8 seconds indicates an override 

request that has not been fulfilled.

The Word "Override" On The Display:

The word 

“Override”

 indicator in the top left corner illu-

minates when the sensor is signalled by the “Status” input 
(Terminal 1). 

This is initiated from the Override/Reset Button at first and 

then confirmed from the “Status” input code which keeps the 

“Override” indicator on.

Figure 9: Override word on the display

Summary of Contents for 910121754

Page 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Page 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Page 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Page 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Page 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Page 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Page 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Page 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Page 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Page 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Page 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Page 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Page 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Page 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Page 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...