Daikin McQuay 910121754 Installation & Maintenance Data Download Page 12

Page 12 of 16 / IM 1171-3

Optional Technician Adjustments

Note:

  If P1 is changed, then P4 and P5 must be changed to 

set desired setpoint values.

P2  

Temperature Offset

 (Factory set to zero).

    • “UP” to increase offset up to +2.
    • “DOWN” to decrease offset down to -2.

P3  

Humidity Offset

 (Factory set to zero).

    • “UP” to increase offset up to +5 
    • “DOWN” to decrease offset down to -5.

P4  

Setpoint Low Range

 (Factory set to 55°F or 13°C 

depending on J50 °F/°C setting).

 

P1 in S1 Mode:

  Adjustment range 55 to 65°F or 13 to 

18°C.

    • “UP” to increase the low setpoint range up to 65°F  

  or 18°C.

    • “DOWN” to decrease the low setpoint range down  

  to 55°F or 13°C.

  

P1 in S2 Mode:

  Adjustment range -3 to -5°F or -1.6 

to -2.8°C.

    • “UP” to increase the low setpoint range by -3°F or  

  -1.6°C. 

    • “DOWN” to decrease the low setpoint range by -5°F  

  or -2.8°C.

P5   

Setpoint High Range

 (Factory set to 95°F or 35°C 

depending on J50-°F/°C setting).

  

P1 in S1 Mode:

 Adjustment range 85 to 95°F or 29 to 

35°C.

    • “UP” to increase the high setpoint range up to 95°F  

  or 35°C.

    • “DOWN” to decrease the high setpoint range down  

  to 85°F or 29°C.

  

P1 in S2 Mode:

 Adjustment range 3 to 5°F or 1.6 to 

2.8°C.

    • UP” to increase the high setpoint range by 5°F or  

 2.8°C.

    • “DOWN” to decrease the high setpoint range by 3°F  

  or 1.6°C.

P6  Fan Lock Mode

 (Factory set to Unlocked “UnL”)

    • “UP/DOWN” to set Fan Lock mode. Choose from  

  list below:

All Models  

UnL   Enables fan to be controlled by the  

 

 

Sensor Fan button

All Models  

FA   Locks fan to the Fan Auto position  

 

 

(No Sensor Fan button control)

WSHP Models   FO   Locks fan to the Fan On position  

 

 

(No Sensor Fan button control)

FCU Models   FH   Locks fan to the Fan High speed  

 

 

position (No Sensor Fan button  

 

 control)

FCU Models   Fd   Locks fan to the Fan Medium speed  

 

 

position (No Sensor Fan button control)

FCU Models   FL   Locks fan to the Fan Low speed  

 

 

position (No Sensor Fan button control)

FCU Models   Fo   Locks fan to the Fan Off position  

 

 

(No Sensor Fan button control)

P7 

System Lock Mode

 (Factory set to Unlocked “UnL”)

    • “UP/DOWN” to set System Lock mode. Choose  

  from list below:

UnL

  

Enables System to be controlled by the Sensor 
System Mode button.

UH

  

Locks System to the Heat mode (No Sensor 

System button control).

UC

  

Locks System to the Cool mode (No Sensor 

System button control).

UA

  

Locks System to the Auto mode (No Sensor 

System button control).

UO

  

Locks System to the Off mode (No Sensor Sys

-

tem button control).

UD

  

Locks System to the Dhum mode (No Sensor 

System button control).

P8

  

Display Resolution (Factory set to ±0.5 resolution, “0.5”).

 

0.1

   “UP/DOWN” to set resolution to ±0.1, (Rounds up  

  at .05).

 

0.5

   “UP/DOWN” to set resolution to ±0.5, (Rounds up  

  at .08).

 

1

   “UP/DOWN” to set resolution to ±1.0, (Rounds up at .5).

P9 

Dehumidification Dead band (DB)

 (Factory set to 

2%), (WSHP Only).

 

  “UP/DOWN” to set Dead band at 2% (On at setpoint 

SP, Off at SP-DB).

 

3

   “UP/DOWN” to set Dead band at 3% (On at setpoint 

SP, Off at SP-DB).

 

  “UP/DOWN” to set Dead band at 4% (On at setpoint 

SP, Off at SP-DB).

 

5

   “UP/DOWN” to set Dead band at 5% (On at setpoint 

SP, Off at SP-DB).

P10  

Display Mode

 (Factory set to #16 for WSHP units,

 

factory set to #4 for FCU Units).

    • “UP/DOWN” to set display mode. 
    • Choose from numbered list below. Choices 5-16 will  

  not be shown if P12 = nOH.

  1 =   No value on the main display (Blank).
  2 =   Temperature Value (TV).

 

3 =   Temperature Setpoint (TSP).

  4 =   Temperature Value & Temperature Setpoint (FCU  

  Default).

  5 =   Humidity Value (HV).
  6 =   Temperature Value & Humidity Value.
  7 =   Humidity Value & Temperature Setpoint.
  8 =   Temperature Value, Temp Setpoint & Humidity  

  Value.

Summary of Contents for 910121754

Page 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Page 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Page 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Page 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Page 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Page 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Page 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Page 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Page 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Page 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Page 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Page 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Page 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Page 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Page 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...

Page 16: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your local...

Reviews: