Daikin McQuay 910121754 Installation & Maintenance Data Download Page 13

IM 1171-3 / Page 13 of 16

Optional Technician Adjustments

 

9 =   Humidity Setpoint (HSP).

  10 =  Temperature Value & Humidity Setpoint.
  11 =  Temperature Setpoint & Humidity Setpoint.
  12 =  Temperature Value & Temp Setpoint & Humidity  

 Setpoint.

  13 =  Humidity Value & Humidity Setpoint.
  14 =  Temperature Value, & Humidity Value &    

  Humidity Setpoint. 

  15 = Humidity Value & Temperature Setpoint &    

  Humidity Setpoint.

  16 =  Temperature Value & Temperature Setpoint &  

  Humidity Value & Humidity Setpoint (WSHP  

  Default).

P11  Setpoint Button Lockout

 (Factory set to “0”: Temp. 

& Humidity Setpoint Enabled. 

Note:

 Selections in P11 will impact Menu P10).

0

     Both Temperature & Humidity Setpoints are enabled 

(No Setpoint lockout, WSHP Units Only).

1

   

Humidity Setpoint Only is Enabled (Temperature 

setpoint is locked out, WSHP Units Only).

2

   

Temperature Setpoint Only is Enabled (Humidity 

setpoint is locked out).

3

    Both Temperature & Humidity Setpoints are Disabled 

(Full Setpoint lockout).

P12 

Dehumidification Enable/Disable

    

nOH

 Dehumidification is Disabled (Factory default  

  for FCU Units).

    

HuA

 Dehumidification is Enabled (Factory default  

  for WSHP Units).

P13  

Occupancy Button Enable/Disable

 (Factory set to 

enabled “ObE”).

    

ObE

 Occupancy Button Enabled (Factory default)

    

Obd

 Occupancy Button Disabled

P14  

Firmware Version - XXX.X

P15    For Units with a BACnet or LonWorks    

  Communications Module

Setpoint Calibration Offset (Factory set to “0”.) 
•  “UP” to increase offset up to +100 will raise the 

MicroTech III perceived set point from the sensor.

•  “DOWN” to decrease offset down to -100. This will lower 

the MicroTech III perceived set point from the sensor.

Calibrate the displayed set point to the set point value sent 

to the MicroTech III as follows:

1. 

  Set the digital room sensor displayed set point to 90° F.

2.    Observe the local set point via the BAS/EMS connected 

by the BACnet or LonWorks Communications Module.

3. 

  Adjust the Configuration Menu P15 on the sensor until 

the local set point and the displayed set point are equal.

P15  For Units without a BACnet or LonWorks 

Communications Module

Setpoint Calibration Offset (Factory set to “0”.)
•  “UP” to increase offset up to +100 will raise the 

MicroTech III perceived set point from the sensor.

•  “DOWN” to decrease offset down to -100. This will lower 

the MicroTech III perceived set point from the sensor.

The Setpoint Calibration Offset can be calculated using the 
following formula:

  ROUND [(Controller Vdd / Sensor Vdd )*1000]-1000

 

Example:

    Given: Controller Vdd = 5.15VDC
    Sensor Vdd = 4.95 VDC

The programmed Calibration Offset would be 

[(5.15/4.95)*1000] -1000 = 40

Summary of Contents for 910121754

Page 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Page 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Page 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Page 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Page 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Page 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Page 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Page 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Page 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Page 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Page 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Page 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Page 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Page 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Page 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...

Page 16: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your local...

Reviews: