Daikin McQuay 910121754 Installation & Maintenance Data Download Page 7

IM 1171-3 / Page 7 of 16

Mounting

Location

Avoid mounting on outside walls or in direct sunlight.

Junction Box, (J-Box)

1.  Pull the wire through the wall and out of the junction box, 

leaving about six inches free.

2.  Pull the wire through the hole in the base plate.

3.  Secure the back plate to the box using the #6-32 × 1/2 

inch mounting screws provided.

4.  Screw the plate firmly to the wall so the foam plate 

backing is compressed about 50%.

5.  Terminate the unit according to the guidelines in the 

Termination section.

6.  Attach Cover by latching it to the top of the base, rotating 

it down and snapping into place.

7.  Secure the cover by backing out the lock-down screws 

using a 1/16" Allen wrench until it is flush with the bottom 

of the cover.

Figure 6: Junction box mounting (hardware is provided 
for both junction box and drywall installation.)

Cover lockdown screws 1/16

"

 allen

Mounting 
base plate

Drywall Mounting

1.  Place the base plate against the wall where you want to 

mount the sensor.

2.  Mark out the two mounting holes where the unit will be 

attached to the wall. Drill a 3/16" hole in the center of 

each mounting hole and insert a drywall anchor into the 
holes.

3.  Drill one 1/2" hole in the middle of the marked wiring 

through hole area.

4.  Pull the wire through the wall and out the 1/2" hole, 

leaving about six inches free.

5.  Pull the wire through the hole in the base plate.
6.  Secure the base to the drywall anchors using the #6 × 1" 

mounting screws provided.

7.  Screw the plate firmly to the wall so the foam plate 

backing is compressed about 50%.

8.  Terminate the unit according to the guidelines in the 

Termination section.

9.  Attach cover by latching it to the top of the base, rotating 

it down and snapping it into place.

10. Secure the cover by backing out the lock-down screws 

using a 1/16" Allen wrench until it is flush with the sides 

of the cover

Note:   in any wall-mount application, the wall temperature 

and the temperature of the air within the wall cavity 
can cause erroneous readings.

 

The mixing of room air and air from within the wall 
cavity can lead to condensation, erroneous readings 
and sensor failure. To prevent these conditions, Daikin 
McQuay recommends sealing the conduit leading to 

the junction box with fiberglass.

Maintenance

Wipe the display as needed with a damp water only cotton 

cloth. Do not use any type of cleaner as it may damage the 

buttons or scratch the display. Do not paint.

Terminal Descriptions

R ...........

15 to 28VAC* (AC requires separate shielded wire) 

(Shield terminated at power source only)

DH

 ........

Dehumidification Contact (Triac from R to DH 

@170mA, WHSP Only).

U ........... Unoccupied Contact. (Terminal grounded when in 

Unoccupied, VDC only).

E ........... System “Off” Indication. (Terminal grounded when 

in System “Off” mode, VDC only).

1............ Status Indicator Input from the MicoTech III Smart-

Source Unit Controller. (5VDC).

2............

Output Signal, and Fan Mode System (0 to 5VDC). 

Output Signal, System Mode Select for FCU only, (0 

to 5VDC).

3............

Output Signal, Setpoint Adjust from 55º to 95˚F (de

-

fault) or ±5º Configurable. (0 to 5VDC) See Setpoint 

Analog Range Tolerances. 

See Table 3

.

4............

Output Signal, Room Temp Thermistor Sensor. (10K 

ATP Z curve, 10K-2).

5

............

Ground or Neutral* (AC requires separate shielded 

wire). Common Reference for All Signal Terminals.

6

............

Output Signal, Fan Speed Select for FCU only. (0 to 

5VDC). Terminal 6 not used for WSHP units.

Note:   * The AC power wiring at terminals [R] & [5] should 

be run in a separate twisted shielded pair to avoid 

possible fluctuating and inaccurate signal levels 

induced into the other sensor signal wires.

 

This sensor AC power can be run in the same conduit 
with the sensor signal wire as long as it’s run in 
twisted, shielded pair and terminated properly.

Summary of Contents for 910121754

Page 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Page 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Page 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Page 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Page 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Page 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Page 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Page 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Page 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Page 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Page 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Page 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Page 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Page 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Page 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...

Page 16: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your local...

Reviews: