background image

Q-222-031 

 

 

7.3 Electrical strength, Mechanical strength 

 

Item 

Specification 

Insulation 
resistance 

Between electric circuit and case (ground). 

50MΩ or more at DC500V 

Between auxiliary supply terminals and input, output 
terminals. 
Between input terminals and output terminals. 

Voltage test 

(Power frequency 
withstand voltage) 

Between electric circuit and case (ground). 

AC2210V (50/60Hz) 5 seconds or 
AC2000V (50/60Hz) 1 minute 

Between auxiliary supply terminals and input, output 
terminals. 
Between input terminals and output terminals. 

Impulse voltage 
test 

Between electric circuit and case (ground).  
(Output circuits are grounded) 

5kV 1.2/50μs 
(Both positive and negative 
polarity, for 3 times each) 

Between auxiliary supply terminals and input terminals.  
(Other circuits are grounded) 
Between input terminals and auxiliary supply terminals.  
(Other circuits are grounded) 
Between voltage input terminals. 
(Other circuits are grounded) 
Between auxiliary supply terminals.  
(Other circuits are grounded) 

Continuation 
over-input 

Input 

1.2 times continuation of rated voltage, rated current. 

Aux. supply 

1.2 times continuation of rated voltage (AC power supply, DC200/220V, DC24V) 
1.3 times continuation of rated voltage (DC100/110V) 
DC57V continuous (DC48V) 

Short time 
over-input 

Input 

2 times 10 seconds of rated voltage. 

once 

2 times 1 second of rated voltage. 

10 times, 10 second intervals 

40 times 1 second and 20 times 4 seconds  
and 10 times 16 seconds of rated current. 

2 times, 1 minute intervals 

10 times 1 second of rated current. 

5 times, 5 minute intervals 

1.5 times 30 minutes of rated current. 

once 

Aux. supply  1.5 times 10 seconds of rated voltage. 

once 

Vibration 

JIS C 60068-2-6    Sweep frequency range:10 to 55 to 10Hz, Displacement amplitude  

 (one-sided amplitude):0.15mm, Number of sweep cycles:10 times 

Shock 

JIS C 60068-2-27   Peak acceleration:500m/s

2

 (when screw is installed),  

300m/s

2

 (when IEC/DIN rail is installed) 

 
 

7.4 Noise immunity 

 

Item 

Specification 

Damped oscillatory 
wave immunity test 
JEA B-402 

Error within ±10% when peak voltage 2.5kV, frequency 1MHz ±10%, applied 3 times for  
30 seconds. 
・Auxiliary supply circuit (Normal / Common) 
・Voltage input circuit (Normal / Common) 
・Current input circuit (Common) 

Square impulse 
immunity test 
JEA B-402 

Error within ±10% when noise (1μs, 100ns width) is repeatedly applied for 5 minutes. 
・Auxiliary supply circuit (Normal / Common)  Over 1.5kV 
・Voltage input circuit (Normal / Common) 

Over 1.5kV 

・Current input circuit (Common) 

Over 1.5kV 

・Output circuit (Induction) 

Over 1.0kV 

Radio wave 
immunity test 

Error within ±10% when radio waves (5W) in the 150MHz and 400MHz bands are  
intermittently irradiated at 1m, and radio waves from mobile phones and wireless  
LAN (2.4GHz, 5GHz) at 0.5m. 

Electrostatic 
discharge immunity 
JEA B-402 

Conducted under normal usage conditions. 
Air discharge:15kV, Contact discharge:8kV, Error within ±10%. 

 

Summary of Contents for FWVTT2-92A-33

Page 1: ...Q 222 031 INSTRUCTION MANUAL POWER FLOW THREE PHASE REACTIVE POWER TRANSDUCER FWVTT2 92A 33...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 8 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Page 5: ...with a width of 35mm The terminal cover is standard equipment 3 Bundled items Inspection certificate 1 Packed in an envelope Terminal screw in a bag M4 screw 5 piece set 1 M4 screw 7 piece set 1 4 Mo...

Page 6: ...this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from the...

Page 7: ...orque 1 0 to 1 3 N m Connection diagram AUX SUPPLY P1 1S 3 1 2 S1 1L 3S S2 P2 OUTPUT A B 3L P3 E LOAD Grounding is class D grounding grounding resistance 100 or less If there is a power line that caus...

Page 8: ...be burdened Especially for voltage output products do not short circuit the output This product will not be damaged even if the output terminal is left open in the current output specifications Howev...

Page 9: ...ess 5 3ms DC48V 3 1A or less 5 3ms Note Refer to the specification code for other ratings 7 2 Performance Item Specification Class index 0 5 Response time 1 second or less Ripple 1 p p or less Fluctua...

Page 10: ...ond of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated current 5 time...

Page 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Page 13: ...g term use please adjust in the next way Remove the terminal cover and VR cap before adjustment and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load w...

Page 14: ...D 400 to 0 to LAG 400var Z Other Z Other Rated current Output Output load range Auxiliary supply 1 AC1A 2 Power transmission DC0 to 0 5 to 1V 200 or more AC80 to 264V Z Other Power receiving DC0 to 0...

Page 15: ...t Output load range Auxiliary supply 2 AC5A 2 Power transmission DC0 to 0 5 to 1V 200 or more AC80 to 264V Z Other Power receiving DC0 to 0 5 to 1V F DC80 to 264V 3 Power transmission DC0 to 2 5 to 5V...

Page 16: ...oad range Auxiliary supply 1 AC1A 2 Power transmission DC0 to 0 25 to 0 5V 200 or more AC80 to 264V Z Other Power receiving DC0 5 to 0 75 to 1V F DC80 to 264V 3 Power transmission DC0 to 1 25 to 2 5V...

Page 17: ...ge Auxiliary supply 2 AC5A 2 Power transmission DC0 to 0 25 to 0 5V 200 or more AC80 to 264V Z Other Power receiving DC0 5 to 0 75 to 1V F DC80 to 264V 3 Power transmission DC0 to 1 25 to 2 5V 600 or...

Page 18: ...Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 FAX 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 FAX 81 774 54 1353 R...

Reviews: