2. Normal Defrost Mode
FUNCTIONS ( Defrost Mode )
HEATER
DEFROTING
PAUSE
FAN DELAY
1) HEATER DEFROSTING
- Defrost heater is switch on until Defrost Sensor temperature reaches 13C.
- Heater operation time
; 30 seconds - Heater is ON free of Defrost Sensor.
; 30 minutes - When Defrost Sensor is
malfunction. ( D1 error )
; 60 minutes - Heater maximum operation time. ( F3 error)
2) PAUSE
- After Defrost Heater switch OFF, Compressor dosen't run within 10 minutes.
3) FAN DELAY
- Freezer & Refrigerator fan switch on after 5miunuts' cmopressor running.
Normal Mode
10min
30min ( D1 error )
60min ( F3 error)
Time
FAN DELAY
OFF
5min
OFF
Refrigerator Fan
OFF
HEATER DEFROST
OFF
OFF
ON
Defrsot Heater
OFF
OFF
OFF
Division
Compressor
Freezer Fan
OFF
ON
PAUSE
OFF
13
Summary of Contents for FRX-623B Series
Page 1: ...FPX6034501...
Page 4: ...2 Outside Diemension SPECIFICATIONS The real features are model dependent 3...
Page 24: ...WIRING DIAGRAM Basic Model 23...
Page 25: ...WIRING DIAGRAM Full Models 24...
Page 26: ...WIRING DIAGRAM Full Models_Inverter Comp 25...
Page 32: ...Evaporator in detail How to Disassemble Assemble for each part 31...
Page 34: ...7 Refrigerator Damper changing method How to Disassemble Assemble for each part 33...
Page 39: ...HOW TO Disassemble Assemble for each part 38...
Page 41: ...2 Freezing or cooling failure Weak cooling TROUBLE SHOOTING 40...
Page 44: ...6 Dews on Refrigerator Compartment TROUBLE SHOOTING 43...
Page 45: ...5 Refrigeration failure Foods does not get cool or cold soon TROUBLE SHOOTING 44...
Page 57: ...COOLING CYCLE HEAVY REPAIR Brzing Reference Drawings 56...