35
Description
1. After the power ON/OFF button is pressed once, the relay and triac are turned ON or OFF per the remote
control setpoint.
– TRIAC is controlled per the fan speed selection.
– RELAY is controlled per the operation mode selection.
2. If the power ON/OFF button is pressed once more, the relay and triac are turn off and the unit stops
operation.
3. The unit turns on or off according to the temperature set point by sensing the room air temperature through
thermistor.
4. If the fan speed selection is set to the auto position, the fan speed is automatically controlled according to the
temperature differance between room temperature and temperature set point.
5. If you press the ON/OFF button during operating the unit, Relay and LED is OFF and the unit is OFF.