Confirm following statement.
When the unit operates normally, Sometimes the outdoor unit and indoor unit cannot operate.
1
Check the function is it timer mode?
2
The function is in the sleep mode and is the setting time over?
3
Is the setting mode DEHUMIDIFIER mode?
4
When the unit is DEHUMIDIFIER mode while in the auto mode, the outdoor unit and indoor unit
sometimes does not run.
The power is applied to the unit
Check the voltge between
and
of terminal block
Y
L
Check the
Breaker or Fuse
Self Diagnostic
function is ON
Check according to
self Diagnostic function
Control P.C.B defect
Check the indoor unit display
is the display all off?
Press the ON/OFF switch of
Remote Control
Is the indoor unit display all off?
Pull out the power plug
and then insert the power plug
after 5 second
Control P.C.B is normal
Recheck from the beginning
Rating voltage more than 90%
Rating voltage
under 90%
No
No
No
Yes
Yes
Neither Indoor Unit nor Outdoor Unit Runs
Summary of Contents for DMB-1812LH
Page 36: ...36 5 WIRING DIAGRAM ...
Page 47: ...PCBDRIVINGDESCRIPTION ...
Page 48: ...1 PCB CIRCUIT DIAGRAM DMB 1812LH Outdoor ...
Page 49: ......
Page 50: ...DMB 1812LH 12K ...
Page 51: ......
Page 52: ...DMB 1812LH 9K ...
Page 53: ......
Page 77: ...74 6 U9 KIA7042P RESET IC KIA70 42P OUTLINE INPUT GROUND OUTPUT VCC 1 3 2 OUT GND ...
Page 81: ...78 3 EXPLODED DIAGRAM Indoor Unit DMB 1812LH 9K ...
Page 83: ...80 DMB 1812LH 12K ...
Page 86: ...83 4 EXPLODED DIAGRAM Outdoor Unit DMB 1812LH ...
Page 88: ...85 5 CONTROL BOX ASSEMBLY DMB 1812LH 9K ...
Page 90: ...87 DMB 1812LH 12K ...
Page 92: ...89 DMB 1812LH Outdoor ...