Set Group On/Off
Data Format
Set Group To
Value
On
255
Off
0
Command Format
Query and Reply
CC1000
Address
5
Reg-H
Reg-L
Group
On/Off
0
CRC-L
CRC-H
Group to Register Address Conversion
❖
Reg = Group
Activate Pattern
Data Format
✦
Patterns can only be activated, the activation code is 255, there is no off for a pattern.
Command Format
Query and Reply
CC1000
Address
5
Reg-H
Reg-L
255
0
CRC-L
CRC-H
Pattern to Register Address Conversion
❖
Reg = P 63
Set DO On/Off
Data Format
Set DO To
Value
On
255
Off
0
Command Format
Query and Reply
CC1000
Address
5
Reg-H
Reg-L
DO On/Off
0
CRC-L
CRC-H
LT to Register Address Conversion
❖
Reg = (LT + 31) x 8 + (DO - 1)