Command & Data Formats
Command & Data Formats
Read DO Status
Command Format
✦
N = 1 to 32
Query
CC1000
Address
3
Reg-H
Reg-L
0
N
CRC-L
CRC-H
Reply
CC1000
Address
3
Nx2
Data1-H
Data1-L
. . .
DataN-H
DataN-L
CRC-L
CRC-H
Data Format
Byte
Bit #
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-H (high byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
Data-L (low byte)
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Bit State
DO
LT
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n+1 (even)
LT n (odd)
LT n (odd)
LT n (odd)
LT n (odd)
LT n (odd)
LT n (odd)
LT n (odd)
LT n (odd)
LT to Register Address Conversion
❖
Reg = (LT-1) div 2
Read DI Status
Command Format
✦
N = 1 to 64
Query
CC1000
Address
3
Reg-H
Reg-L
0
N
CRC-L
CRC-H
Reply
CC1000
Address
3
Nx2
Data1-H
Data1-L
. . .
DataN-H
DataN-L
CRC-L
CRC-H
Data Format
Byte
Bit #
High Byte
High Byte
High Byte
High Byte
High Byte
High Byte
High Byte
High Byte
Low Byte
Low Byte
Low Byte
Low Byte
Low Byte
Low Byte
Low Byte
Low Byte
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Bit State
DI
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
LT to Register Address Conversion
❖
Reg = LT+31
CC1000 Modbus Reference 2.10e
!
14/122