Read AO Upper Limit
Command Format
✦
N = 1 to 125
Query
CC1000
Address
3
Reg-H
Reg-L
0
N
CRC-L
CRC-H
Reply
CC1000
Address
3
Nx2
0
Data1-L
. . .
0
DataN-L
CRC-L
CRC-H
Data Format
✦
AO Upper Limit = Data-L x 1%
LT to Register Address Conversion
❖
Reg = (LT+703) x 4 + (AO-1)
Read AO Lower Limit
Command Format
✦
N = 1 to 125
Query
CC1000
Address
3
Reg-H
Reg-L
0
N
CRC-L
CRC-H
Reply
CC1000
Address
3
Nx2
0
Data1-L
. . .
0
DataN-L
CRC-L
CRC-H
Data Format
✦
AO Lower Limit = Data-L x 1%
LT to Register Address Conversion
❖
Reg = (LT+767) x 4 + (AO-1)
CC1000 Modbus Reference 2.10e
!
21/122