Figure 3: Connections 

5.5

 

Electrical Connections of Inputs and Outputs 

The MCE-22/C has 3 digital inputs, 2 NTC inputs for fluid temperature measurement T and T1 an analogue input and 2 digital outputs 
so as to be able to make certain interfaces with more complex installations. 
Shown in 

Figure 4, Figure 5 

and 

Figure 6

 for example, are some possible configurations of the inputs and outputs. 

For the installer it will be sufficient to wire up the desired input and output contacts and to configure their functions as desired (see par. 
5.5.1 par. 5.5.2 and par. 5.5.4) 

 

5.5.1

 

Digital Inputs 

The digital inputs are screen-printed at the base of the 18-pole terminal board: 
-

 

I1: Terminals 16 and 17 

-

 

I2: Terminals 15 and 16 

-

 

I3: Terminals 13 and 14 

-

 

I4: Terminals 12 and 13 

 

The inputs may be powered with either direct or alternating current. Shown below are the electrical characteristics of the inputs (see 

Table 4

Electrical characteristics of the inputs 

 

 

DC inputs [V] 

AC inputs [Vrms] 

Minimum switch-on voltage [V] 

Maximum switch-off voltage [V] 

1.5 

Maximum admissible voltage [V] 

36 

36 

Current absorbed at 12V  [mA] 

3.3 

3.3 

Max. accepted cable section [mm²] 

2.13 

N.B. The inputs can be controlled with any polarity (positive or negative with respect to their earth connection)

 

Table 4: Electrical characteristics of the inputs  

 

The example proposed in

 

Figure 4 

refers to the connection with a dry contact using the internal voltage to control the inputs.

 

 

 

ATTENTION

: The voltage supplied between terminals 11 and 18 of J5 (18-pole terminal board) is 

19 Vdc

 and may distribute maximum 

50 mA

 

If you have a voltage instead of a contact, it can still be used to control the inputs: it will be sufficient 

not

 to use the terV and 

GND  and to connect the source of voltage to the desired input, respecting the characteristics described in 

Table 4. 

 

 

ATTENTION: The pairs of inputs I1/I2 and I3/I4 have one pole in common for each pair.

 

Summary of Contents for MCE-22/C

Page 1: ...NANCE INSTALLATIONS UND WARTUNGSANLEITUNGEN INSTRUCTIES VOOR INSTALLATIE EN ONDERHOUD INSTRUCCIONES DE INSTALACI N Y MANTENIMIENTO INSTALLATIONS OCH UNDERH LLSANVISNING KURMA VE BAKIM B LG LER INSTRUC...

Page 2: ...ITALIANO pag 01 FRAN AIS page 17 ENGLISH page 33 DEUTSCH seite 49 NEDERLANDS pag 65 ESPA OL p g 81 SVENSKA sid 97 113 T RK E sf 129 145 ROMANA pag 161 SLOVEN INA Stran 177 193 MAGYAR Old 209...

Page 3: ...ng Lights 44 9 MENU 44 10 FACTORY SETTINGS 48 11 TYPES OF ALARM 48 12 MODBUS MCE C 48 13 BACNET 48 1 KEY The frontispiece shows the version of this document in the form Vn x This version indicates tha...

Page 4: ...may still have dangerous voltage when the motor is stopped 3 APPLICATIONS The inverter of the MCE C series is a device conceived for the management of circulation pumps allowing integrated regulation...

Page 5: ...must be chosen according to the regulations in force The table 2 supplies an indication on the section of the cable to be used to supply power to the inverter The table refers to 3 core PVC cables ph...

Page 6: ...mm 10 m 20 m 30 m 40 m 50 m 60 m 70 m 80 m 90 m 100 m 120 m 140 m 160 m 180 m 200 m 4 A 1 5 1 5 1 5 1 5 2 5 2 5 2 5 2 5 4 4 4 6 6 6 10 8 A 1 5 1 5 2 5 2 5 4 4 6 6 6 10 10 10 10 16 16 12 A 1 5 2 5 4 4...

Page 7: ...e electrical characteristics of the inputs see Table 4 Electrical characteristics of the inputs DC inputs V AC inputs Vrms Minimum switch on voltage V 8 6 Maximum switch off voltage V 2 1 5 Maximum ad...

Page 8: ...et point reduction function in remote mode I3 Quick Start If input 3 is activated from the control panel the pump is started at the quick start frequency Fq see advanced menu I4 Not enabled Figure 5 E...

Page 9: ...portion to the input voltage 0 10V itself see par 0 and par 9 The input A2V is not enabled Figure 6 Example of Connection of Analogue Input N B The 0 10V analogue input is mutually exclusive with the...

Page 10: ...uts listed below refer to the two 3 pole terminal boards J3 and J4 indicated with the screen printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal NC Normally Close...

Page 11: ...follows 1 hold down the central menu key for 5 seconds 2 scroll through the parameters until you see ET 3 increase the value of the ET parameter in the advanced menu until the noise disappears For the...

Page 12: ...e par 9 7 1 4 Regulation with Proportional Differential Pressure In this adjustment mode the differential pressure is reduced or increased as the water request falls or rises This mode may be set by m...

Page 13: ...ample if T1 50 C dTs T T1 13 75 C when the temperature T1 is between 40 C and 70 C the circulator works to keep the absolute difference between T and T1 constant at a dTs inversely proportional to the...

Page 14: ...he yellow light is lit Red light Warning of an alarm malfunction present in the system If the light is blinking it is a non blocking alarm and the pump can still be controlled If the light is fixed it...

Page 15: ...luid temperatures T and T1 1 10000 K Td Running time of the hydraulic circuit it acts in an inversely proportional way on the regulating speed in the T and DT regulations 0 1800 s Bs Parameter for set...

Page 16: ...point is set from Page 3 0 Depending on the type of regulation chosen on the previous page the set point to be set will be a head Hs a frequency Fs a temperature Ts or a difference in temperature dTs...

Page 17: ...rs Liquid temperature measured on the input A1V 18 pole terminal block Liquid temperature measured on the input A2V 18 pole terminal block T Temperature difference of the liquid T T1 in absolute value...

Page 18: ...Error e22 e30 Voltage Error e31 Protocol Error e32 e35 Excess temperature e37 Low voltage e38 High voltage e39 e40 Excess current e42 Dry operation e43 e44 e45 e54 Pressure Sensor e46 Pump Disconnecte...

Reviews: