FACTORY SETTINGS 

Parameter

 

Value

 

Regulating mode 

 = Regulation with constant differential pressure 

Hs (Differential Pressure Set-point) 

50% of the max. pump head (see inverter sensitive parameters 

set in factory) 

Fs (Frequency Set-point) 

90% of the pump rated frequency 

Tmax 

50 ºC 

Operating mode 

auto 

Set-point reduction percentage 

50 % 

Twin operating mode 

 = Alternate every 24h 

Pump start control 

EXT (from remote signal on input I1). 

 

11.

 

TYPES OF ALARM 

Alarm Code

 

Alarm Symbol

 

Alarm Description

 

e0 - e16;  e21 

 

Internal Error 

e17 - e19 

 

Short Circuit 

e20 

 

Voltage Error 

e22 - e30 

 

Voltage Error 

e31 

 

Protocol Error 

e32 - e35 

 

Excess temperature  

e37 

 

Low voltage 

e38 

 

High voltage 

e39 - e40 

 

Excess current 

e42 

 

Dry operation 

e43; e44; e45; e54 

 

Pressure Sensor 

e46 

 

Pump Disconnected 

 

 

Booster mode activated in an operation mode not allowed. 

e55 

 

Temperature sensor T error 

e56 

 

Temperature sensor T1 error 

Table 7: List of Alarms 

 

12.

 

MODBUS MCE-C 

The use of the Modbus protocol is allowed, through the installation of the cable kit 60193518 MCE MODBUS CABLE KIT.   

For more information, see the web page 

https://dabpumps.com/mce-c

. 

 

13.

 

BACNET 

 

The use of the Bacnet protocol is allowed, through the installation of a Bacnet-Modbus gateway.   
For more information and access to the list of recommended devices, see the web page 

https://dabpumps.com/mce-c

. 

 

Summary of Contents for MCE-22/C

Page 1: ...NANCE INSTALLATIONS UND WARTUNGSANLEITUNGEN INSTRUCTIES VOOR INSTALLATIE EN ONDERHOUD INSTRUCCIONES DE INSTALACI N Y MANTENIMIENTO INSTALLATIONS OCH UNDERH LLSANVISNING KURMA VE BAKIM B LG LER INSTRUC...

Page 2: ...ITALIANO pag 01 FRAN AIS page 17 ENGLISH page 33 DEUTSCH seite 49 NEDERLANDS pag 65 ESPA OL p g 81 SVENSKA sid 97 113 T RK E sf 129 145 ROMANA pag 161 SLOVEN INA Stran 177 193 MAGYAR Old 209...

Page 3: ...ng Lights 44 9 MENU 44 10 FACTORY SETTINGS 48 11 TYPES OF ALARM 48 12 MODBUS MCE C 48 13 BACNET 48 1 KEY The frontispiece shows the version of this document in the form Vn x This version indicates tha...

Page 4: ...may still have dangerous voltage when the motor is stopped 3 APPLICATIONS The inverter of the MCE C series is a device conceived for the management of circulation pumps allowing integrated regulation...

Page 5: ...must be chosen according to the regulations in force The table 2 supplies an indication on the section of the cable to be used to supply power to the inverter The table refers to 3 core PVC cables ph...

Page 6: ...mm 10 m 20 m 30 m 40 m 50 m 60 m 70 m 80 m 90 m 100 m 120 m 140 m 160 m 180 m 200 m 4 A 1 5 1 5 1 5 1 5 2 5 2 5 2 5 2 5 4 4 4 6 6 6 10 8 A 1 5 1 5 2 5 2 5 4 4 6 6 6 10 10 10 10 16 16 12 A 1 5 2 5 4 4...

Page 7: ...e electrical characteristics of the inputs see Table 4 Electrical characteristics of the inputs DC inputs V AC inputs Vrms Minimum switch on voltage V 8 6 Maximum switch off voltage V 2 1 5 Maximum ad...

Page 8: ...et point reduction function in remote mode I3 Quick Start If input 3 is activated from the control panel the pump is started at the quick start frequency Fq see advanced menu I4 Not enabled Figure 5 E...

Page 9: ...portion to the input voltage 0 10V itself see par 0 and par 9 The input A2V is not enabled Figure 6 Example of Connection of Analogue Input N B The 0 10V analogue input is mutually exclusive with the...

Page 10: ...uts listed below refer to the two 3 pole terminal boards J3 and J4 indicated with the screen printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal NC Normally Close...

Page 11: ...follows 1 hold down the central menu key for 5 seconds 2 scroll through the parameters until you see ET 3 increase the value of the ET parameter in the advanced menu until the noise disappears For the...

Page 12: ...e par 9 7 1 4 Regulation with Proportional Differential Pressure In this adjustment mode the differential pressure is reduced or increased as the water request falls or rises This mode may be set by m...

Page 13: ...ample if T1 50 C dTs T T1 13 75 C when the temperature T1 is between 40 C and 70 C the circulator works to keep the absolute difference between T and T1 constant at a dTs inversely proportional to the...

Page 14: ...he yellow light is lit Red light Warning of an alarm malfunction present in the system If the light is blinking it is a non blocking alarm and the pump can still be controlled If the light is fixed it...

Page 15: ...luid temperatures T and T1 1 10000 K Td Running time of the hydraulic circuit it acts in an inversely proportional way on the regulating speed in the T and DT regulations 0 1800 s Bs Parameter for set...

Page 16: ...point is set from Page 3 0 Depending on the type of regulation chosen on the previous page the set point to be set will be a head Hs a frequency Fs a temperature Ts or a difference in temperature dTs...

Page 17: ...rs Liquid temperature measured on the input A1V 18 pole terminal block Liquid temperature measured on the input A2V 18 pole terminal block T Temperature difference of the liquid T T1 in absolute value...

Page 18: ...Error e22 e30 Voltage Error e31 Protocol Error e32 e35 Excess temperature e37 Low voltage e38 High voltage e39 e40 Excess current e42 Dry operation e43 e44 e45 e54 Pressure Sensor e46 Pump Disconnecte...

Reviews: