ENGLISH 

 

46 

 

 

Page 2.0 

 

 

The regulating mode is set from Page 2.0. It is possible to choose from 9 different modes: 

1.

 

 = Regulation with constant differential pressure 

2.

 

 = Regulation with constant curve with speed set from the display. 

3.

 

 = Regulation with constant curve with speed set by remote signal 0-10V. 

4.

 

 = Proportional  differential pressure regulation. 

5.

 

=

 

T constant regulation increasing mode 

6.

 

= T constant regulation decreasing mode 

7.

 

= T1 constant regulation increasing mode 

8.

 

= T1 constant regulation decreasing mode 

9.

 

= ∆T constant regulation 

Page 2.0 displays the three icons which represent: 

 

central icon = setting currently selected 

 

right icon = next setting 

 

left icon = previous setting 

Page 3.0 

 

 

 

 

 

 

 

The regulating set-point is set from Page 3.0. 

Depending on the type of regulation chosen on the previous page, the set-point to be set will be a head 
(

Hs

), a frequency (

Fs

), a temperature (

Ts

) or a difference in temperature (

dTs

). 

Page 5.0 

 

 

Page 5.0 is displayed in all pressure regulating modes and allows the setting of “auto” or “economy” 
operating mode. 

“Auto” mode disables the reading of the status of digital input I2 and in fact the system always activates 
the set-point set by the user. 

“Economy” mode enables the reading of the status of digital input I2. When input I2 is energised the 

system activates a percentage reduction of the set-point set by the user (Page 6.0). 

For the connection of the inputs see par. 5.5.1 

 

Page 6.0 

 

 

Page  6.0  is  displayed  if  “economy”  mode  has  been  chosen  on  page  5.0  and  allows  setting  of  the 
percentage reduction value of the set-point. 

This reduction will be carried out if digital input I2 is energised.  

 
 
 
 
 
 

Summary of Contents for MCE-22/C

Page 1: ...NANCE INSTALLATIONS UND WARTUNGSANLEITUNGEN INSTRUCTIES VOOR INSTALLATIE EN ONDERHOUD INSTRUCCIONES DE INSTALACI N Y MANTENIMIENTO INSTALLATIONS OCH UNDERH LLSANVISNING KURMA VE BAKIM B LG LER INSTRUC...

Page 2: ...ITALIANO pag 01 FRAN AIS page 17 ENGLISH page 33 DEUTSCH seite 49 NEDERLANDS pag 65 ESPA OL p g 81 SVENSKA sid 97 113 T RK E sf 129 145 ROMANA pag 161 SLOVEN INA Stran 177 193 MAGYAR Old 209...

Page 3: ...ng Lights 44 9 MENU 44 10 FACTORY SETTINGS 48 11 TYPES OF ALARM 48 12 MODBUS MCE C 48 13 BACNET 48 1 KEY The frontispiece shows the version of this document in the form Vn x This version indicates tha...

Page 4: ...may still have dangerous voltage when the motor is stopped 3 APPLICATIONS The inverter of the MCE C series is a device conceived for the management of circulation pumps allowing integrated regulation...

Page 5: ...must be chosen according to the regulations in force The table 2 supplies an indication on the section of the cable to be used to supply power to the inverter The table refers to 3 core PVC cables ph...

Page 6: ...mm 10 m 20 m 30 m 40 m 50 m 60 m 70 m 80 m 90 m 100 m 120 m 140 m 160 m 180 m 200 m 4 A 1 5 1 5 1 5 1 5 2 5 2 5 2 5 2 5 4 4 4 6 6 6 10 8 A 1 5 1 5 2 5 2 5 4 4 6 6 6 10 10 10 10 16 16 12 A 1 5 2 5 4 4...

Page 7: ...e electrical characteristics of the inputs see Table 4 Electrical characteristics of the inputs DC inputs V AC inputs Vrms Minimum switch on voltage V 8 6 Maximum switch off voltage V 2 1 5 Maximum ad...

Page 8: ...et point reduction function in remote mode I3 Quick Start If input 3 is activated from the control panel the pump is started at the quick start frequency Fq see advanced menu I4 Not enabled Figure 5 E...

Page 9: ...portion to the input voltage 0 10V itself see par 0 and par 9 The input A2V is not enabled Figure 6 Example of Connection of Analogue Input N B The 0 10V analogue input is mutually exclusive with the...

Page 10: ...uts listed below refer to the two 3 pole terminal boards J3 and J4 indicated with the screen printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal NC Normally Close...

Page 11: ...follows 1 hold down the central menu key for 5 seconds 2 scroll through the parameters until you see ET 3 increase the value of the ET parameter in the advanced menu until the noise disappears For the...

Page 12: ...e par 9 7 1 4 Regulation with Proportional Differential Pressure In this adjustment mode the differential pressure is reduced or increased as the water request falls or rises This mode may be set by m...

Page 13: ...ample if T1 50 C dTs T T1 13 75 C when the temperature T1 is between 40 C and 70 C the circulator works to keep the absolute difference between T and T1 constant at a dTs inversely proportional to the...

Page 14: ...he yellow light is lit Red light Warning of an alarm malfunction present in the system If the light is blinking it is a non blocking alarm and the pump can still be controlled If the light is fixed it...

Page 15: ...luid temperatures T and T1 1 10000 K Td Running time of the hydraulic circuit it acts in an inversely proportional way on the regulating speed in the T and DT regulations 0 1800 s Bs Parameter for set...

Page 16: ...point is set from Page 3 0 Depending on the type of regulation chosen on the previous page the set point to be set will be a head Hs a frequency Fs a temperature Ts or a difference in temperature dTs...

Page 17: ...rs Liquid temperature measured on the input A1V 18 pole terminal block Liquid temperature measured on the input A2V 18 pole terminal block T Temperature difference of the liquid T T1 in absolute value...

Page 18: ...Error e22 e30 Voltage Error e31 Protocol Error e32 e35 Excess temperature e37 Low voltage e38 High voltage e39 e40 Excess current e42 Dry operation e43 e44 e45 e54 Pressure Sensor e46 Pump Disconnecte...

Reviews: