Figure 12: APP page for setting Modbus parameters 

 

The characteristics of the Modbus connection are as follows (the options at the first start-up are shown in bold): 

 

Parameter 

Description 

Settable values 

Baud rate (bps) 

Transmission speed 

2400, 4800, 9600, 

19200

, 38400, 57600, 

115200 

Parity 

Parity check

 

No

, Even, Odd 

Stop bit 

Number of stop bits

 

1

.2 

Minimum response delay (ms) 

Minimum response time (e.g., if 100, Esy I/O will 

respond to the message after at least 100ms)

 

0

 – 1000  

Id 

Slave identification (each slave device on the Modbus 

network must have a different Id)

 

1

-247 

Table 7: Modbus characteristics 

 

For information on Modbus registers that can be consulted and/or modified, refer to the manual of the device connected to Esy I/O.  

 

IMPORTANT!

 In order to use the Modbus peripheral, enable it via APP by configuring the Modbus Mode parameter. 

 

2.11

 

Fault management 

 

 Table 8 Describes possible faults that may be encountered by Esy I/O.  

 

Fault 

FAULT LED  

General  

On with fixed light  

Insufficient supply voltage  

1 blink  

Pressure sensor error (if sensor use is set)  

2 blinks  

Internal error 

3… 7 blinks 

Wireless  

8 blinks 

Wifi 

9 blinks 

Table 8: List of faults 

 

 

Summary of Contents for ESY I/O

Page 1: ...TRUCCIONES DE INSTALACI N Y MANTENIMIENTO ES INSTRUCTIES VOOR INSTALLATIE EN ONDERHOUD NL RU POKYNY K INSTALACI A DR B CZ INSTRUKCJA MONTA U I KONSERWACJI PL INSTRU ES PARA A INSTALA O E A MANUTEN O P...

Page 2: ...firmwareversies 1 x x NL 1 x x RU N vod plat pro verze maj c firmware 1 x x CZ Instrukcja wa na dla wersji firmware 1 x x PL Manual v lido para as vers es firmware 1 x x PT K ytt opas laiteohjelmavers...

Page 3: ...ISH page 13 FRAN AIS page 25 DEUTSCH seite 37 ESPA OL p g 49 NEDERLANDS pag 61 73 E TINA strana 85 POLSKI strona 97 PORTUGU S pag 109 SUOMI sivu 121 SVENSKA sid 133 ROM N pag 145 157 T RK E sf 169 MAG...

Page 4: ...ust comply with the local safety regulations in force in the country in which the product is installed Everything must be done in a workmanlike manner Failure to respect the safety regulations not onl...

Page 5: ...he following applications connection to BMS Build Management Systems equipped withRS485 MODBUS RTU interface Connection with clean contact inputs e g floats Output connection e g sirens Connection of...

Page 6: ...m2 AWG 18 Maximum sheath diameter 10mm Minimum sheath diameter 5mm 1 Insert the cable in the cable gland shown in Figure 1 circled in orange Cable gland 3 Figure 1 Front view of cable glands 2 Connect...

Page 7: ...rror present see paragraph 2 10 Off No error Pressure Green On Pressure sensor connected Off Pressure sensor not connected Modbus Green Red Steady green Gateway modbus active Regular blinking green Mo...

Page 8: ...better use of the services offered by the product Before starting to use the product make sure that it is updated to the latest software version available During the software update the products invol...

Page 9: ...AC inputs 50 60 Hz Vrms Minimum switch on voltage V 6 2 4 5 Maximum switch off voltage V 2 1 5 Maximum admissible voltage V 40 40 Current absorbed at 12V mA 1 4 1 4 Max accepted cable section mm 1 5...

Page 10: ...cs of the output contacts Type of contact NO Normally open Max bearable voltage V 230 VAC Max bearable current A 5 resistive load 2 5 inductive load Max accepted cable section mm 2 5 Table 4 Character...

Page 11: ...evice group of devices see associated product manual The output status is displayed both by the Output LEDs see Table 1 and on the APP Status page see Figure 7 Figure 7 Output Status Display 2 9 Remot...

Page 12: ...ual Via the Dconnect APP it is possible to select the sensor used Figure 9 Pressure Sensor Setting Page The following sensors are currently supported 1 HUBA pressure sensor 0 25 bar 2 10 RS485 Modbus...

Page 13: ...tion is always of the Daisy chain type option 1 Do not use star option 2 or ring connections The termination resistors if necessary must be inserted in the first and last device on the bus e g Figure...

Page 14: ...00 Id Slave identification each slave device on the Modbus network must have a different Id 1 247 Table 7 Modbus characteristics For information on Modbus registers that can be consulted and or modifi...

Page 15: ...wiring of sensors inputs and outputs Pressure sensor error Pressure sensor out of range Check that the pressure sensor connection is correct PR1 connector Green pressure sensor led not active Although...

Page 16: ...dwtgroup com info belgium dwtgroup com Tel 32 2 4668353 Tel 32 2 4668353 DAB PUMPS IBERICA S L DAB PUMPS IBERICA S L Calle Verano 18 20 22 Calle Verano 18 20 22 28850 Torrej n de Ardoz Madrid 28850 T...

Reviews: