Wiring 

Modbus communication with 2-wire RS485 contemplates the use of 3 cables (A, B and GND). Connect the 3 cables correctly. 

It is recommended to use a screened 2-pole cable, with a twisted pair, adapted to 120 ohm if termination resistors are to be used. 

 

Figure 10: Rs485 Modbus Wiring 

 

MODBUS Terminals

 

Description 

 

Terminal - 

 

Te 

 

GND 

Reference 

Table 6: Description of Rs485 Terminals 

 

The typical connection with an RS485 BUS is shown below. 

The recommended connection is always of the Daisy chain type (option 1). Do not use star (option 2) or ring connections. The termination 

resistors, if necessary, must be inserted in the first and last device on the bus (e.g. Figure 11: The termination resistors must be inserted in 

Master BMS

 and 

Device n

) Figure 11: Examples of bus

 wiring

The maximum recommended number of connected devices is 32, consistent with other devices in the network. The length of the cables 

depends on the baud rate chosen, i.e. the higher the baud rate, the shorter the cable length.  

 

Figure 11: Examples of bus wiring 

 

Parameter configuration  

 

Esy I/O parameters are configured via Dconnect APP, connecting point-to-point via smartphone. 

 

Summary of Contents for ESY I/O

Page 1: ...TRUCCIONES DE INSTALACI N Y MANTENIMIENTO ES INSTRUCTIES VOOR INSTALLATIE EN ONDERHOUD NL RU POKYNY K INSTALACI A DR B CZ INSTRUKCJA MONTA U I KONSERWACJI PL INSTRU ES PARA A INSTALA O E A MANUTEN O P...

Page 2: ...firmwareversies 1 x x NL 1 x x RU N vod plat pro verze maj c firmware 1 x x CZ Instrukcja wa na dla wersji firmware 1 x x PL Manual v lido para as vers es firmware 1 x x PT K ytt opas laiteohjelmavers...

Page 3: ...ISH page 13 FRAN AIS page 25 DEUTSCH seite 37 ESPA OL p g 49 NEDERLANDS pag 61 73 E TINA strana 85 POLSKI strona 97 PORTUGU S pag 109 SUOMI sivu 121 SVENSKA sid 133 ROM N pag 145 157 T RK E sf 169 MAG...

Page 4: ...ust comply with the local safety regulations in force in the country in which the product is installed Everything must be done in a workmanlike manner Failure to respect the safety regulations not onl...

Page 5: ...he following applications connection to BMS Build Management Systems equipped withRS485 MODBUS RTU interface Connection with clean contact inputs e g floats Output connection e g sirens Connection of...

Page 6: ...m2 AWG 18 Maximum sheath diameter 10mm Minimum sheath diameter 5mm 1 Insert the cable in the cable gland shown in Figure 1 circled in orange Cable gland 3 Figure 1 Front view of cable glands 2 Connect...

Page 7: ...rror present see paragraph 2 10 Off No error Pressure Green On Pressure sensor connected Off Pressure sensor not connected Modbus Green Red Steady green Gateway modbus active Regular blinking green Mo...

Page 8: ...better use of the services offered by the product Before starting to use the product make sure that it is updated to the latest software version available During the software update the products invol...

Page 9: ...AC inputs 50 60 Hz Vrms Minimum switch on voltage V 6 2 4 5 Maximum switch off voltage V 2 1 5 Maximum admissible voltage V 40 40 Current absorbed at 12V mA 1 4 1 4 Max accepted cable section mm 1 5...

Page 10: ...cs of the output contacts Type of contact NO Normally open Max bearable voltage V 230 VAC Max bearable current A 5 resistive load 2 5 inductive load Max accepted cable section mm 2 5 Table 4 Character...

Page 11: ...evice group of devices see associated product manual The output status is displayed both by the Output LEDs see Table 1 and on the APP Status page see Figure 7 Figure 7 Output Status Display 2 9 Remot...

Page 12: ...ual Via the Dconnect APP it is possible to select the sensor used Figure 9 Pressure Sensor Setting Page The following sensors are currently supported 1 HUBA pressure sensor 0 25 bar 2 10 RS485 Modbus...

Page 13: ...tion is always of the Daisy chain type option 1 Do not use star option 2 or ring connections The termination resistors if necessary must be inserted in the first and last device on the bus e g Figure...

Page 14: ...00 Id Slave identification each slave device on the Modbus network must have a different Id 1 247 Table 7 Modbus characteristics For information on Modbus registers that can be consulted and or modifi...

Page 15: ...wiring of sensors inputs and outputs Pressure sensor error Pressure sensor out of range Check that the pressure sensor connection is correct PR1 connector Green pressure sensor led not active Although...

Page 16: ...dwtgroup com info belgium dwtgroup com Tel 32 2 4668353 Tel 32 2 4668353 DAB PUMPS IBERICA S L DAB PUMPS IBERICA S L Calle Verano 18 20 22 Calle Verano 18 20 22 28850 Torrej n de Ardoz Madrid 28850 T...

Reviews: