ENGLISH
49
continued from the previous page
Number of Pages
Parameter
Description
Field
Unit of
measure
DAB
Extended
SetUp
20. Min.Pres.Al.H2O
Pressure set point to be set based on the pressure in
the delivery circuit.
The system is stopped if the pressure falls below
the set point for more than 1 minute: the display
shows
AL H2O
.
Attempted automatic reset 3 times after one minute
and total block with manual reset at the fourth
intervention. At this point the control unit indicates
AL 64: water lack.
0,00-:-25,5 bar
0,5
21.Flow.Unit.Meas.
Choice of the unit of measure of the flow meter:
L/sec. – L/min. – M³h.
L/sec.
L/min.
M³h.
L/sec.
L/min.
M³h.
M³h.
22. Flow sensor f.s.
Choice of the full-scale value of the flow meter.
00
23. TA calib.factor
Coefficient for calibrating the amperometric
transformer
00
24. TV calib.factor
Coefficient for calibrating the voltmetric
transformer
00
26. Pumps Mnt.Interv.
Setting of the pump maintenance hours.
Mnt.Interv. P1, Mnt.Interv. P2, Mnt.Interv.P3,
Mnt.Interv. P4
0-:-99999 hours
4500
27. Op. Hours P1
Hours worked by pump P1
0-:-99999 hours
28. Op. Hours P2
Hours worked by pump P2
0-:-99999 hours
29. Op. Hours P3
Hours worked by pump P3
0-:-99999 hours
30. Op. Hours P4
Hours worked by pump P4
0-:-99999 hours