DAAB OUTPUT CARD DB407 INSTRUCTION MANUAL
4
Functions using add-in card DB407
With DB410 installed there is access to five programmable relay outputs and one triac output. These outputs are grouped
into three groups with two common positions. Note that the positions located closest to the printed circuit board on each
terminal are the common positions. These positions are marked i1, i2 and i3. The outputs are the upper terminal positions.
Functions of programmable outputs 1 - 6
The instructions are identical for all six programmable outputs, apart from the channel number – output 1 has
channel number o1nn, output 2 has channel number o2nn, etc. The settings below are for output 1.
Activate programmable output 1 by setting o100 to the desired function. A value of 0 means that the output is
disabled (open) regardless of the settings of other channels.
If you set the value to 1, the output can be used as a traffic light signal based on the position indication. Movement
and warning time signals are also available with this setting. The value 2 is for presence detection in the vehicle loop,
the value 3 is for motor locks, and the value four turns the output into an alarm output.
Channel o110 Open position
Set to 1 for a constant signal in the open position.
Channel o111 Mid position
Set 1 to obtain constant signal in mid position.
Channel o112 Closed position
Set 1 to obtain constant signal in closed position.
Example for a green light: o110 = 1, o111 = 0, o112 = 0.
Example for a red light: o110 = 0, o111 = 1, o112 = 1.
Channel o113 Movement
Use this channel to specify function during movement. The function will be active as soon as the door starts moving.
See the channel reference for the available options. Only output 4 is able to send a flashing signal.
Channel o120 Warning time before start
Settable time 0.00 – 9.59 minutes, where 0.0 means closed. Which function is to be warned is selected in o121.
Channel o121 Warning function in combination with channel o120
Set value 1 to obtain constant signal before automatic close, 2 to obtain constant signal before park and automatic
close, 3 to obtain constant signal before close signal, park and automatic close, 4 for signal before all control signals.
Channel o122 Function during warning
Select 1 if the output signal is to be disabled during storing in any output.
Select 2 if the output is to continue to indicate position or movement regardless of warning.
Channel o130 Delay for alarms specified in o131 and o132. The alarm is delayed by the set time of 0.00 – 9.59
minutes. The factory setting is 0.00.
Channel o131-o142 Alarm in different conditions
If it is set to 1, the output gives a signal when the condition, according to the channel specification, has been fulfilled
for longer than the time set in o130.
Select the output to be normally open or normally closed by setting channel o183 to:
The value 1 is for normally open (NO) and the value 2 is for normally closed (NC).
Channel o191 Function when LOOP1, LOOP2 or PHOTO are activated:
Used to set the presence detection required from the vehicle loop. See the channel reference for the available options.
Function of programmable output 4
In principle, programmable output 4 is the same as outputs 1, 2, 3, 5 and 6, except that it is a triac output. The settings
are the same for outputs 1 to 6, except that the alternative for flashing signal only exists for output 4. See the channel
reference for the channel settings.