DAAB OUTPUT CARD DB407 INSTRUCTION MANUAL

4

Functions using add-in card DB407

With DB410 installed there is access to five programmable relay outputs and one triac output. These outputs are grouped 

into three groups with two common positions. Note that the positions located closest to the printed circuit board on each 

terminal are the common positions. These positions are marked i1, i2 and i3. The outputs are the upper terminal positions.

Functions of programmable outputs 1 - 6

The instructions are identical for all six programmable outputs, apart from the channel number – output 1 has 

channel number o1nn, output 2 has channel number o2nn, etc. The settings below are for output 1. 

Activate programmable output 1 by setting  o100 to the desired function. A value of 0 means that the output is 

disabled (open) regardless of the settings of other channels. 

If you set the value to 1, the output can be used as a traffic light signal based on the position indication. Movement 

and warning time signals are also available with this setting. The value 2 is for presence detection in the vehicle loop, 

the value 3 is for motor locks, and the value four turns the output into an alarm output.
Channel o110 Open position 

Set to 1 for a constant signal in the open position.
Channel o111 Mid position 

Set 1 to obtain constant signal in mid position.
Channel o112 Closed position 

Set 1 to obtain constant signal in closed position.
Example for a green light: o110 = 1, o111 = 0, o112 = 0. 

Example for a red light: o110 = 0, o111 = 1, o112 = 1.
Channel o113 Movement 

Use this channel to specify function during movement. The function will be active as soon as the door starts moving. 

See the channel reference for the available options. Only output 4 is able to send a flashing signal.
Channel o120 Warning time before start 

Settable time 0.00 – 9.59 minutes, where 0.0 means closed. Which function is to be warned is selected in o121.
Channel o121 Warning function in combination with channel o120 

Set value 1 to obtain constant signal before automatic close, 2 to obtain constant signal before park and automatic 

close, 3 to obtain constant signal before close signal, park and automatic close, 4 for signal before all control signals.
Channel o122 Function during warning 

Select 1 if the output signal is to be disabled during storing in any output. 

Select 2 if the output is to continue to indicate position or movement regardless of warning.
Channel o130 Delay for alarms specified in o131 and o132. The alarm is delayed by the set time of 0.00 – 9.59 

minutes. The factory setting is 0.00.
Channel o131-o142 Alarm in different conditions 

If it is set to 1, the output gives a signal when the condition, according to the channel specification, has been fulfilled 

for longer than the time set in o130.
Select the output to be normally open or normally closed by setting channel o183 to: 

The value 1 is for normally open (NO) and the value 2 is for normally closed (NC).
Channel o191 Function when LOOP1,  LOOP2 or PHOTO are activated: 

Used to set the presence detection required from the vehicle loop. See the channel reference for the available options.

Function of programmable output 4

In principle, programmable output 4 is the same as outputs 1, 2, 3, 5 and 6, except that it is a triac output. The settings 

are the same for outputs 1 to 6, except that the alternative for flashing signal only exists for output 4. See the channel 

reference for the channel settings.

Summary of Contents for DB407

Page 1: ...atic control unit DAAB EP104 with software version 4 07 INSTRUCTION MANUAL DAAB OUTPUT CARD DB407 FAAC Nordic AB BOX 125 SE 284 22 PERSTORP SWEDEN 46 435 77 95 00 support faac se www faac se R e v i s i o n 1 1 ...

Page 2: ...04 All the outputs have programmable function Output functions are set on EP104 If output o4 is used the supply voltage must be of AC type alternating current as this output is of the triac type Note that i2 is common to o3 and o4 The status of the outputs indicated by LEDs installed at the top of the card A lit LED indicates closed function Installation 1 Discharge any static charge in your body ...

Page 3: ...ble ties as close to the terminal as possible Connection must be performed by a qualified electrician L N o1 o2 i1 o3 o4 i2 o5 o6 i3 i1 i2 i3 L N L N 230VAC 24VDC NB AC only if o4 is used 230VAC 24VDC 230VAC 24VDC DB407 If o4 is used for AC and o3 is to be used for DC o3 can control an interposing relay When the board has been installed and connected the power supply to EP104 can be switched on ...

Page 4: ...e active as soon as the door starts moving See the channel reference for the available options Only output 4 is able to send a flashing signal Channel o120 Warning time before start Settable time 0 00 9 59 minutes where 0 0 means closed Which function is to be warned is selected in o121 Channel o121 Warning function in combination with channel o120 Set value 1 to obtain constant signal before auto...

Page 5: ...re is a break in a cable or the EP104 loses its power supply Specify the following settings to use output 1 for fence alarm o100 1 Position indication o110 1 Signal in open position o111 1 Signal in mid position o113 3 Signal in opening closing movement o114 Delay in switch off at least 1 second according to alarm manufacturer s instructions o120 Warning test before start according to the alarm ma...

Page 6: ...he opening movement 2 Constant signal in the closing movement 3 Constant signal in the opening and closing movement 4 No signal during movement used in combination with o110 o111 and o112 o114 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o120 Warning time before start 0 00 9 59 minutes 0 00 o121 Warn...

Page 7: ...nstant signal o134 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o135 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o136 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o137 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o138 Alarm if vehicle loop 2 is activated 0 1 0 0 Disabled 1 Constant signal o139 Alarm if photocell ...

Page 8: ...tion Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are acti...

Page 9: ...vement 2 Constant signal in the closing movement 3 Constant signal in the opening and closing movement 4 No signal during movement used in combination with o210 o211 and o212 o214 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o220 Warning time before start 0 00 9 59 minutes 0 00 o221 Warning function ...

Page 10: ...onstant signal o234 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o235 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o236 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o237 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o238 Alarm if vehicle loop 2 is activated 0 1 0 0 Disabled 1 Constant signal o239 Alarm if photocell...

Page 11: ...tection Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are a...

Page 12: ...ing movement 2 Constant signal in the closing movement 3 Constant signal in the opening and closing movement 4 No signal during movement used in combination with o310 o311 and o312 o314 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o320 Warning time before start 0 00 9 59 minutes 0 00 o321 Warning fun...

Page 13: ...onstant signal o334 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o335 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o336 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o337 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o338 Alarm if vehicle loop 2 is activated 0 1 0 0 Disabled 1 Constant signal o339 Alarm if photocell...

Page 14: ...detection Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are...

Page 15: ...the opening and closing movement 4 No signal during movement used in combination with o410 o411 and o412 5 Flashing signal in the opening movement 6 Flashing signal in the closing movement 7 Flashing signal in the opening and closing movement o414 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o420 War...

Page 16: ... 1 0 0 Constant signal 1 Active o433 Alarm if stop circuit interrupted 0 1 0 0 Disabled 1 Constant signal o434 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o435 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o436 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o437 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o438 Alar...

Page 17: ...tion Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are acti...

Page 18: ...movement 2 Constant signal in the closing movement 3 Constant signal in the opening and closing movement 4 No signal during movement used in combination with o510 o511 and o512 o514 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o520 Warning time before start 0 00 9 59 minutes 0 00 o521 Warning functio...

Page 19: ...onstant signal o534 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o535 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o536 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o537 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o538 Alarm if vehicle loop 2 is activated 0 1 0 0 Disabled 1 Constant signal o539 Alarm if photocell...

Page 20: ...ction Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are act...

Page 21: ...ovement 2 Constant signal in the closing movement 3 Constant signal in the opening and closing movement 4 No signal during movement used in combination with o610 o611 and o612 o614 Delayed switch off Switch off after the specified time For example to switch off lighting a specified time after closing 0 00 9 59 minutes 0 00 o620 Warning time before start 0 00 9 59 minutes 0 00 o621 Warning function...

Page 22: ...Constant signal o634 Alarm if door open 0 1 0 0 Disabled 1 Constant signal o635 Alarm if door is in mid position 0 1 0 0 Disabled 1 Constant signal o636 Alarm if door is in closed position 0 1 0 0 Disabled 1 Constant signal o637 Alarm if vehicle loop 1 is activated 0 1 0 0 Disabled 1 Constant signal o638 Alarm if vehicle loop 2 is activated 0 1 0 0 Disabled 1 Constant signal o639 Alarm if photocel...

Page 23: ...tion Signal when PHOTO LOOP1 and LOOP2 are activated remains until either PHOTO LOOP1 or LOOP2 is clear 08 Presence detection Signal when either LOOP1 or LOOP2 is activated remains until either LOOP1 or LOOP2 is clear 09 Direction sensing Signal when first LOOP1 and then LOOP2 are activated The signal remains until LOOP2 is clear 10 Direction sensing Signal when first LOOP1 and then PHOTO are acti...

Page 24: ......

Reviews: