After connecting the ignition lance, turning on the control switch and pressing the push-button: 

 

 

Fault 

Possible cause 

Remedy   

 

 

No firing spark  

Power cut 

Charge batteries, 

LED off 

 

check fuse in the igniter 

 

 

 

replace fuse, if necessary  

 

 
LED lights only briefly 

Defective spark plug 

Replace spark plug  

 

 

 

(see section “Repairs”) 

 
 

 

HV-cable not properly 

Connect cable at the  

 

 

connected 

electronics casing   

 
 

 

Defective spark gap 

Replace spark gap  

 

 

 

(see section “Repairs”) 

 
 
 

6.  

Repairs 

 

Warning! 

 
Only  suitably  qualified staff  is  authorized to  exchange  the  wear  parts.  Use  only  original spares. 

Disconnect the battery charger during any repair work. Put switch S1 in its O-position before work-

ing on the appliance. Remove fuse F 1 (see Fig. 3) immediately after opening the cover lid. When 

repairing the spark plug, disconnect the HV-cable from the igniter (by pulling out the HV-plug). 

 

6.1.   Replacing the high-energy-spark plug 

 

  Disconnect the HV-cable from the igniter 

  Unscrew the worn-out high-energy spark plug 

(warning: high temperatures can be possible!)

 

  Slide off the protective tube from the replacement plug; the thread has been treated with a 

high-temperature paste (which prevents the spark plug from getting stuck in the socket) 

  Insert the new spark plug into the ignition lance and screw it in finger-tight 

  Re-assemble the plug-in reversed order 

 
 
 
 
 
 
 

 

Summary of Contents for BZ - V 24 TK

Page 1: ...Internationales Know How in der Flammen berwachung International Know How in Flame Detection Operating Instructions Portable Burner Igniter BZ V 24 TK...

Page 2: ...harger at the appliance inlet 4 2 Operating principle 5 3 Start up 5 4 Battery charger 6 4 1 Technical data of the battery charger 6 5 Faults break downs 7 6 Repairs 7 6 1 Replacing the high energy sp...

Page 3: ...ol switch underneath the appliance inlet for connecting the battery charger and the igniter will be activated by pressing the push button please observe the start up instructions A yellow LED installe...

Page 4: ...10 1 2 Casing configuration Fig 1 200 230 1 3 Connection of the battery charger at the appliance inlet Fig 2 1 2 3 4 5 6 protective conductor PE green yellow free charging voltage free free free blue...

Page 5: ...t be used If the red LED is on the discharge voltage is reached and the startup to be omitted and the batteries to be recharge immediately The igniter must only be started with the ignition lance insi...

Page 6: ...the cable socket of the spiral cable with the igniter Leave switch S1 at the igniter in the OFF position The green LED lamp indicating ready for operation and the red LED charging indicator at the ba...

Page 7: ...the wear parts Use only original spares Disconnect the battery charger during any repair work Put switch S1 in its O position before work ing on the appliance Remove fuse F 1 see Fig 3 immediately aft...

Page 8: ...approx 1 600 V for the ignition process will be generated in the appliance which may still be applied for to the HV capacitor and to the spark gap for a few seconds although the igniter has been swit...

Page 9: ...S 1 H 2 7 Maintenance Because of its heavy duty design the igniter does not require any maintenance Should deposits settle on the spark plug due to the plant s specific conditions they can be removed...

Page 10: ...possibly errors or defects may cause an exchange Requirement is that an error can be attributed to defects in components or manufacture The warranty is void if procedures are performed by the user or...

Reviews: