99.824.31 1.2/03/12
ZA-BSY+
8/20
English
Closing edge protection
Main closing edge
Beside
closing
edge
Beside
closing
edge
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
Type
Power supply
24 VDC, ±15%
24 VDC, ±15%
24 VDC, ±15%
24 VDC, ±15%
Nominal current
0,5 A (1,2 A)
1,0 A (2,0 A)
1,2 A (2,2 A)
1,4 A (2,5 A)
Nominal force
300 N
800 N
1000 N
1500 N
Nominal locking force
1100 N
Lifetime
>10 000 double strokes
Duty cycle
30 % (With cycle time 10 minutes)
Housing
nodized aluminium / polycarbonate
Ingress protection
IP 65
Temperature range
-5 ... +75°C
Fire stability
30 min / 300°C
Nominal stroke length*
ee type plate
Additional functions *
losing edge protection activated (3 stroke repeatings)
* Programmable with software SW-BSY+
ZA35-BSY+(-HS)
ZA85-BSY+(-HS)
ZA105-BSY+(-HS)
ZA155-BSY+(-HS)
A
S
C
Running speed and forces
Normal operation =
SHEV- fast running =
I
III
77mm
23mm
7,1
mm/s
5 mm/s
5 mm/s
~7,1
mm/s
/
~8
mm/s
(~17
mm/s)
II
Closure
Ranges
Technical data
All forces
+ approx. 20 % switch-off reserve
(temporary)
OPEN
Forces
CR
III
CR
II
CR
I
300 N
300 N
300 N
300 N
800 N
800 N
800 N
800 N
1000 N
1000 N
1000 N
800 N
1500 N
1000 N
1000 N
800 N
ZA 35
ZA 85
ZA 105 ZA 155
CLOSE