Smoke Vent Button

Place(s) of mounting:

Maximal 8 smoke vent buttons can be
connected.
Main control must be mounted on ground-floor
according to VdS 2221.
Secondary control is to be installed in all other
floor levels according to VdS 2221.
Install buttons so, that they are accessible
any time and clearly visible.

Mounting height:

1,5m above upper edge of firm flooring.

Fastening:

With plug screws 4,5 x 40mm diagonal, or
direct on 55mm flush box with 2 screws.

Housing colour:

Standard: deep orange (RAL 2011),
according to VdS 2592.
However, deviating colours might be locally
required (e.g. grey, blue, yellow, red).
Please consult your D+H distributor.

Drives

Smoke and heat vent opening:

Smoke gases are to be carried off as
unhindered as possible through smoke and
heat vent opening in case of  fire.
According to relevant rules, openings have
to be placed always in the upper part of a
building.
The smoke and heat vent opening can be
mounted in the wall as well as in the ceiling.
Size, kind and arrangement of the opening
is of decisive significance for an optimal
effect of the smoke and heat vent system.
The important thing here is, that an escape
must not be hindered by the window wing
itself, by structural facts like offsets, or the
like.
Minimum ventilating surface is given by le-
gal regulations and structural facts. The
smoke vent opening must be at least 1m² or
5% of the basis, dependent on the LBO.
The valuated sizes of opening angles of
smoke and heat vent systems must be in
agreement with the responsible fire
protection authority.
Observe! Window wings, opening inward, must
not project in escape/ and rescue routes and
obstruct them.

High-Speed function:

All D+H drives with SHEV high-speed
function are supported. In daily ventilation
operation, a considerable noise reduction
is achieved through the reduced drive speed.
In case of SHEV the drives run - triggered
through the orange monitoring line - with a
very high speed to reach the OPEN position
defined within 60 seconds at the most.

Mounting of the drives:

Please take mounting informations from the
relevant instruction for use of the respective
drive, because of varied possibilities for
choosing drives.

Attention:
When Dip switch 8 is on ON, the smoke
vent will be triggered with an OPEN-
impulse every 2 minutes for a duration of
30 minutes according to VdS 2581. For this,
the drive must be  blockage safe according
to  VdS 2580 par. 4.7. . All  D+H drives meet
this precondition. Otherwise Dip switch 8
is to be switched on OFF.

Summary of Contents for RZN 4416-M

Page 1: ...orized by the manufacturer Green control diodes in the buttons must constantly lighten otherwise see Informations for Starting Repair power failure at once Emergency power supply for 72 hours drive gr...

Page 2: ...Maintenance Guarantee Piktograph explanation 2 Technical Data Accumulator Control TID 3 Introduction 4 View motherboard RZN 4416 K 5 Drives and smoke vent buttons 6 Wiring plan 7 Connection cables 8...

Page 3: ...al discharge of accumulator the control panel will switch off In this case smoke vent is no longer ensured In this case a malfunction will be no more indicated either Technical Data Rated voltage 230...

Page 4: ...Insurer against damage of property VdS and the respective local authorities Recommended is that maintenance work should be carried out by authorized specialist companies only Only regular and profess...

Page 5: ...reset indicator fuse accumulator accumulator connection LED failure accumulator charging voltage control accumulator fire recognition element thermo maximum signal ground short DIP switch S6 control p...

Page 6: ...hat an escape must not be hindered by the window wing itself by structural facts like offsets or the like Minimum ventilating surface is given by le gal regulations and structural facts The smoke vent...

Page 7: ...mer Fire detector 24VDC FO 1362 or FT 1262 Wiring Plan Paragon 230 V Supply Provide for separate electric circuit Mark fuses Plug covering cap over mains binder on motherboard of control panel Connect...

Page 8: ...ause of a large variety on the market Please consult your D H distributor about these The smoke vent control panel is designed for opening smoke vent devices which operate by thermal ascending force a...

Page 9: ...ector THE 4 RZN 4416 M RM MOT branch box Length of line and cross sections see page 12 last RT 43 N 10kW alarm control line line malfunction closed 2 7 8 3 1 6 4 line control alarm closed 2 3 1 6 4 7...

Page 10: ...4 5 6 7 8 RZN 4416 M line control alarm closed RM RT Smoke vent button RT 43 H Smoke vent button RT 43 N 10kW alarm alarm control control line line line line malfunction closed closed 2 2 7 8 7 3 3 1...

Page 11: ...vent button lane 2nd RT 43 H RT 43 H RT 43 N RT 43 N 10kW alarm alarm control control line line line line malfunction malfunction closed closed 2 2 7 7 8 8 3 3 1 1 6 6 4 4 alarm alarm zu zu red red gr...

Page 12: ...losed open signal optional N open monitoring Mot a Mot b 5 6 7 1 2 3 4 1 1 2 2 optional RM RT LT 3 4 5 6 7 8 line control alarm closed external excitiation vent button LT 43 SD fire detector Typ opera...

Page 13: ...e vent button 1st lane RT 42 Smoke vent button 2nd lane RT 42 10kW RT 42 RT 42 line line line control control control alarm alarm alarm closed closed closed 7 7 7 2 2 2 3 3 3 1 1 1 6 6 6 4 4 5 4 OK OK...

Page 14: ...ctor dependency are employed Connection of several fire detectors Connection of one fire detector N N Z M1 M2 D1 D2 interrupter key magnetic clamp terminal resistor line 10K single fire detector 180R...

Page 15: ...a Mot b derive off in par allel monitoring will be looped through all cables up to group end Example 1 1 lane Simple installation but unfavourable for voltage drop All drives on one line Example 2 2 l...

Page 16: ...special conditions only Performance check alarm reset and ventilation 10k resistance in smoke vent button 10k resistance in fire detector Stop module 2x47k in conduit box Connect mains mains control l...

Page 17: ...e limitation be retriggered again Switch 4 on ON Storage operation in CLOSED direction Switch 4 on OFF Key operation in CLOSED direction Switch 5 on ON Storage operation in OPEN direction Switch 5 on...

Page 18: ...n idle idle idle Bus control Switch 1 on ON Two smoke detectors dependency Attention Switch Smoke detector alarm can be reset only in control panel Dip switch 2 must be switched on OFF when remote res...

Page 19: ...on Ventilating time limitation OPEN retriggering Duty cycle in CLOSED direction Duty cycle in OPEN direction Group CLOSED in case of alarm Group fault on alarm Alarm re clocking OPEN running time limi...

Page 20: ...tector Reset line in control panel switch off switch on press button red display diode extinguishes in button and control panel Press masked button in smoke vent button Smoke vent must be closing The...

Reviews: