16/20
RZN 4416-M Rev.:1.1
yes
no
Factory-set?
(Dip switch)
yes
Delivery condition of DIP-switches
see page 17.
Informations for Starting
Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel.
no
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
All cable
connected?
Partial or incomplete connection of components can
cause malfunction.
Check following connections: mains 230V, drives,
smoke vent buttons, when necessary fire detectors
and vent buttons. See wiring and connection plans
page 9-15.
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
Performance check alarm/reset and ventilation
10k
Ω
resistance in
smoke vent button?
10k
Ω
resistance in
fire detector?
Stop module 2x47k
Ω
in conduit box?
Connect mains
mains control
lightens?
Connect
accumulator lines control
lightens?
Smoke
vent flap opens and
closes?
Cramp stop module on last or only drive in conduit box
on wire 5 yellow, 6 black, 7 black. See connection plan
page 9-15.
Check line safety fuse in E distribution and fuse mains
in control panel.
Mains still not available or line switch
on "
0
" or one of fuses faulty.
Resistance must be cramped in electric last button on
binding posts 3/ 8 (RT 43-H) or binding posts 3/ 7
(RT 42). See connection plan page 9-15.
Resistance must be cramped in last or only fire detector
on binding post 2 and 4 (type FO/FT). Resistance
remains in control panel between binding post RM 1
and 2, when no fire detector available.
See connection plan page 9-15.
Possibly change poles in drive.