RZN 4402-K / RZN 4404-K
99.823.80 2.1/08/12
20/32
English
View motherboard
sec
20
2
60
40
min
15
2
45
30
F1.25A
Reset
0
I
S 1
Ext.
Signals
Ventilation
System
Line
Group
U
F.315A
Fx.xA
Battery
Rauchabzugszentrale
Smoke Vent Controller
2x12V/
x.xAh
1 2 3 4 5 6 7 8 9 10
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
www.dh-partner.com
D+H Mechatronic - Germany - +49 40 605 65 0
IP
30
VDS-Nr.:
RZN 4402/04-K/KS V2
IN :
OUT :
Temp. -5°C...40°C
mains supply
fire recognation
element
fuse drive
LED malfunction group
LED control
LED alarm
LED malfunction line
LED mains
fuse external signals
DIP switch
S1
fuse mains
battery charging
voltage regulator
battery
connection
LED malfunction
battery
fuse battery
Technical data
Type
: RZN 4402/04-K (-KS)
Nominal voltage
: 230 VAC, 50 Hz
Rated power
: 60 VA / 120 VA
Stand-by operating
: 5,6 W / 5,8 W
Protection class
: II (I)
Ingress protection
: IP 30 (IP 54)
Temperature range
: -5°C...+40°C
Output voltage
: 24 VDC / res. ripple. <10%
Safe output
rated current
: 2 A / 4 A
Dimensions
RZN 4402/04-K V2
: 310 x 310 x 100 (WxHxD)
RZN 4402/04-KS V2 : 400 x 300 x 120 (WxHxD)
D+H Highspeed (HS) drives will be supported.
24 V - Emergency supply
Emergency power supply for 72 hours.
RZN 4402-K(S) V2: 2x 12V / 1,2 Ah ±0,2Ah (Type 1)
RZN 4404-K(S) V2: 2x 12V / 2,2 Ah ±0,3Ah (Type 2)
With connection of D+H alarm devices:
RZN 4402-K(S) V2: 2x 12V / 2,2 Ah ±0,3 Ah (Type 2)
RZN 4404-K(S) V2: 2x 12V / 3,4 Ah ±0,3 Ah (Type 8)
Use VdS approved storage batteries only!
(Attention! Bigger housing necessary!)
Note
While an alert, a possible group disturbance will
not notified. Only after reset the alarm, a fault
message will be output.
OPEN running
time limitation
ventilation time
limitation
line
ON-
OFF-RESET
D1
D47 D42 D20
D79
D14
–
+