KA 34: 300** N, 11,8 mm/s =
“-HS” KA 34 12,2 mm/s =
(with tensile force (1/2 nominal load) 16,1 mm/s)
KA 54: 500** N, 11,8 mm/s =
“-HS” KA 54 13,3 mm/s =
(with tensile force (1/2 nominal load) 17,2 mm/s)
Technical data
Type
KA 34/xxx-BSY+
KA 54/xxx-BSY+
Power supply
24 VDC / ±15% / 1,0 A
24 VDC / ±15% / 1,4 A
Nominal force
300 N
500 N
Nominal locking force
1000 N
Lifetime
>10 000 double strokes
Duty cycle
30 % (with cycle time 10 minutes)
Housing
anodized aluminium
Ingress protection
IP 32
Temperature range
-5 ... +75°C
Fire stability
30 min / 300°C
Nominal stroke length *
see type plate
Additional functions *
clamping protection activated (3 stroke repeatings), locking relief activated
* programmable with software SW-BSY+
(with covering stoppers delivered with bracket sets)
Running speed and forces
** + 20 % switch-off reserve
(temporary)
77mm
KA
34:
300**
N,
11,8
mm/s
KA
54:
500**
N,
11,8
mm/s
5 mm/s
150
N
23mm
I
II
III
5mm/s
150
...
250
N
Closure
Ranges
Normal operation =
SHEV- fast running =
8/120
KA-BSY+
English
99.823.89 2.1/07/11
main
closing
edge
beside closing edge
beside
closing edge
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive pinch
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!