Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
8 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Especially silent in ventilation operation
because of reduced motor speed
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Extent of supply
500
600
800
1000
1
100
1200
1300
1400
1500
1600
0
200
400
600
800
1000
1200
1400
max. Load (N)
Stroke (mm)
Permanent
Temporary
Pressure load diagram
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
Safety notes
Safety extra low voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the toothed rack!
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Use option “-W“ in case of outside mounting!
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed red safety slip!
99.824.31 1.4/04/16
Closing edge protection
Main closing edge
Beside closing edge
Beside closing edge
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Type
ZA 35-BSY+(-HS)
ZA 85-BSY+(-HS)
ZA 105-BSY+(-HS)
ZA 155-BSY+(-HS)
Power supply
24 V DC, ±15%
24 V DC, ±15%
24 V DC, ±15%
24 V DC, ±15%
Nominal current
0,5 A (1,2 A)
1,0 A (2,0 A)
1,2 A (2,2 A)
1,4 A (2,5 A)
Nominal force
300 N
800 N
1000 N
1500 N
Nominal locking force
1100 N
Lifetime
>20 000 double strokes
Duty cycle
30 % (With cycle time 10 minutes)
Housing
Aluminium powder-coated (~RAL 9006), polycarbonate
Ingress protection
IP 65 (“-W“ = IP 54)
Temperature range
-5 ... +75°C
Fire stability
30 min / 300°C
Emission sound pressure level LpA ≤ 70 dB(A)
Nominal stroke length*
see type plate
Additional functions *
closing edge protection activated (3 stroke repeatings)
* Programmable with software SCS
Running speed and forces
Normal operation
=
SHEV- fast running =
I
III
77mm
23mm
7,1 mm/s
5 mm/s
5 mm/s
~7,1 mm/s /
~8 mm/s (~17 mm/s)
II
Closure Ranges
Technical data
All forces
+ approx. 20 % switch-off reserve
(temporary)
OPEN
Forces
CR
III
CR
II
CR
I
300 N
300 N
300 N
300 N
800 N
800 N
800 N
800 N
1000 N
1000 N
1000 N
800 N
1500 N
1000 N
1000 N
800 N
ZA 35
ZA 85
ZA 105 ZA 155
CLOSE