D+H DYER ZA 35-BSY+ Instructions Manual Download Page 3

ZA-BSY+

6/20

ZA-BSY+

 

English

Intended use

-   Rack and pinion drive for electric opening and

   closing of windows and flaps in the facade and
   roof area

-   Operating voltage 24 V DC
-   Useable for smoke ventilation, D+H Euro-SHEV

   according to DIN EN 12101-2 as well as daily
   natural ventilation

-   Only for inside mounting

Performance features

-   Micro processor controlled  synchro electronics

   BSY + for a precise  synchronous run of  up to
   8 drives

-   Individually programmable (via software SCS)
-   SHEV-high speed function (fast-running   

   feature in OPEN-direction)

-   Protection system for the main  closing edge
-   Especially silent in ventilation operation 

   because of reduced motor speed

Drive unit with 2,5 m silicone cable. Dependent on 
the  type  of  window, different  bracket  sets  are 
available separately.

Extent of supply

500

600

800

1000

1

100

1200

1300

1400

1500

1600

0

200

400

600

800

1000

1200

1400

max. Load (N)

Stroke (mm)

Permanent

Temporary

Pressure load diagram

Maximum  pressure  load  of  the  toothed  rack  is  not 
automatically identical with maximum pressure force 
of the drive!
Loads from over 1000 N to 1500 N are only briefly 
permissible (e.g. to throwing off snow or with wind 
loads). These may arise up to a stroke of 800 mm.

Safety notes

Safety extra low voltage 24 V DC!

Do not connect directly to the mains supply!
-   Connection has to be carried out only by an

   authorized electrical specialist

-   Danger of violent pressure in handaccessible area
-   Keep away People from the operating area of the

   drive

-   Keep away children from the control
-   Observe pressure load diagram of the toothed rack!
-   Only for inside mounting.

   Use rain detector with danger of rain
   (e.g. at domelights or roof windows)

-   Use option “-W“ in case of  outside mounting!
-   Just use unchanged original D+H parts
-   Observe mounting instructions of bracket set!

Observe enclosed red safety slip!

99.824.31 1.4/04/16

Closing edge protection

Main closing edge

Beside closing edge

Beside closing edge

In  "CLOSE"  direction  the  drive  has  an  active 
protection  for  the  main  closing  edge.  With  an 
overload in the closing range 3 and 2 the drive runs 
"OPEN" for 10 seconds, then drive "CLOSE" again. If 
after  three  attempts  a  closing  is  not  possible,  the 
drive remains in this position.
In addition, the drive has a passive protection. The 
closing speed in closure Range 2 and 1 is reduced to 
5 mm/s.

Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.

WARNING

Read all safety warnings, instructions, illustrations 
and specifications provided with this product.
Failure to follow all instructions listed below may 
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future 
reference.

Type 

ZA 35-BSY+(-HS) 

ZA 85-BSY+(-HS) 

ZA 105-BSY+(-HS) 

ZA 155-BSY+(-HS)

Power supply 

24 V DC, ±15% 

24 V DC, ±15% 

24 V DC, ±15% 

24 V DC, ±15%

Nominal current  

0,5 A (1,2 A) 

1,0 A (2,0 A) 

1,2 A (2,2 A) 

 1,4 A (2,5 A)

Nominal force 

300 N 

800 N 

1000 N 

 1500 N

Nominal locking force 

1100 N

Lifetime 

>20 000 double strokes

Duty cycle 

30 % (With cycle time 10 minutes)

Housing 

Aluminium powder-coated (~RAL 9006), polycarbonate

Ingress protection 

IP 65 (“-W“ = IP 54)

Temperature range 

-5 ... +75°C

Fire stability 

30 min / 300°C

Emission sound pressure level  LpA ≤ 70 dB(A)
Nominal stroke length* 

see type plate

Additional functions * 

closing edge protection activated (3 stroke repeatings)

* Programmable with software SCS

Running speed and forces

Normal  operation

  =

SHEV- fast running =

I

III

77mm

23mm

7,1 mm/s

5 mm/s

5 mm/s

~7,1 mm/s /   

   ~8 mm/s (~17 mm/s)

II

Closure Ranges

Technical data

All forces
+ approx. 20 % switch-off reserve
(temporary)

OPEN

Forces

CR 

III

CR 

II

CR 

I

300 N
300 N
300 N
300 N

800 N
800 N
800 N
800 N

1000 N
1000 N
1000 N

800 N

1500 N
1000 N
1000 N

800 N

ZA 35

ZA 85

ZA 105 ZA 155

CLOSE

Summary of Contents for DYER ZA 35-BSY+

Page 1: ...Standard version Version without tube option OT Please order bracket sets separately B 08 11 22802 026 G 500001 ZA 35 85 105 155 BSY HS instructions...

Page 2: ...load of the toothed rack is not automatically identical with maximum pressure force of the drive Loads from over 1000 N to 1500 N are only briefly permissible e g to throwing off snow or with wind lo...

Page 3: ...1 2 A 1 0 A 2 0 A 1 2 A 2 2 A 1 4 A 2 5 A Nominal force 300 N 800 N 1000 N 1500 N Nominal locking force 1100 N Lifetime 20 000 double strokes Duty cycle 30 With cycle time 10 minutes Housing Aluminium...

Page 4: ...able Disconnect drive from electric voltage 1 Move out toothed rack about 10 20 mm Disconnect drive from electric Voltage 2 Take off drive unit and shift 3 Attention Moving direction of drive is chang...

Page 5: ...ices that are no longer usable must be collected separa tely and disposed of in an environmentally correct manner Disposal Declaration of Conformity We declare under our sole responsibility that the p...

Page 6: ...a BN Mot b OG HS YE Data A GN Data B GY BRV PK n c Standard WH Mot a BN Mot b OG HS YE Data A GN Data B Option SGI WH Mot a BN Mot b OG HS YE Data A GN Data B GY SGI PK SGI Option SKS WH Mot a BN Mot...

Page 7: ...b HS HS Data a Data a Data b Data b ZA BSY ZA BSY Slave s Master Junction box Mot b BN Mot a WH to control panel Monitoring Normal mode SHEV fast running High Speed High Speed High Speed Not in case o...

Page 8: ...6 0 46 104 9 13 6 30 30 9 7 Version without tube option OT 216 9 13 30 55 Nominal stroke 223 Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 1...

Reviews: