D+H CDC 200/600 Original Instructions Manual Download Page 7

99.823.42 2.2/09/13

99.823.42 2.2/09/13

6/16

7/16

English

English

CDC-PC xxxx-T01

* TMS line must 
  be disconnected!

CDC-PC xxxx-T01

*

*

Tandem Safety Function

For the operation of 2-3 drives on separate vents the 
tandem safety function (TMS) may not be used! For 
this  the  TMS  line  (yellow)  of  the  connection  cable 
CDC-PC xxxx of the drives is disconnected, so that 
the remaining drive(s) are still opened in case of fire 
in the event of a failure, under voltage or overload 
cut-out.

Whenever two drives are operated on a single sash, 
the  tandem  safety  function  can  be  used.  This 
function  connects  the  cut-offs  of  the  two  drives  in 
such a way that if one drive is cut off due to overload, 
the other drive will also be cut off.

In this case active jamming protection may not 
activated!

Maintenance and cleaning

Inspection  and  maintenance  has  to  be  carried  out 
according  to  D+H  maintenance  notes.  Only  original 
D+H spare parts may be used. Repair is to be carried 
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft 
cloth.
Do not use cleaning agents or solvents.

Electrical  devices,  accessories  and  packaging 
should be sorted for environmental-friendly recycling.
Do not dispose electrical
devices into household waste!
Only for EC countries:
According  the  European  Guideline 
2002/96/EC  for  waste  electrical  and 
electronic equipment and its implemen-
tation  into  national  right,  electrcal 
devices that are no longer usable must be collected 
separately  and  disposed  of  in  an  environmentally 
correct manner.

Disposal

Guarantee

You will get 

2 years guarantee

 for all D+H products 

from date of verified handing over of the system up to 
maximal  3  years  after  date  of  delivery,  when 
mounting  and  starting  has  been  carried  out  by 

an 

authorized D+H-distributor.

D+H guarantee is expired, with connection of D+H 
components with external systems or with mixing of 
D+H products with parts of other manufacturers.

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 
product  described  under  “Technical  Data”  is  in 
conformity with the following directives:

2004/108/EC, 2006/95/EC

Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek

Thomas Kern

Maik Schmees

Member of the Board

Authorized signatory, Technical Director

12.06.2010

CDC 200/600 (-SBD)

CDC 200/600 (-SBD)

All approx. 20 %
switch-off reserve (temporary)

Technical Data

Type

CDC 200/600

CDC 200/600 -SBD

Rated voltage

24 VDC, ±15%, 1,0 A

24 VDC, ±15%, 0,83 A

Chain type

Standard chain

Side bow chain

Nominal pressure

200 N

150 N

Nominal locking force

approx. 1500 N 

Service life

>10.000 double strokes

Housing 

Aluminium die-casting

Protective system

IP 50

Temp.range

-5 ... +75°C

Fire stability

30 min / 300°C

/

Stroke lenght *  **

max. 600 mm

Additional functions **

Active closing edge protection = deactivated
Locking relief  = activated (Retraction lift max. 0,2 mm)

* Adjustable with PLP 1

** Programmable with PLP 1 and PDA Servicetool

Running speed and forces

Normal operation

      =

SHEV-fast  running  =

CDC 200/600:

= 200 N, 

200 N, 

6,7 mm/s

11,4 mm/s

CDC 200/600-SBD:

= 150 N, 

150 N, 

6,7 mm/s

11,4 mm/s

77 mm

6,7 mm/s

200 N

5 mm/s

150 N

23

Closing Range

Main closing edge

Beside closing edge

Beside - 
closing edge

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 
protection for the main closing edge. If there is an 
overload in the closing ranges 3 and 2, the drive runs 
"OPEN"  for  10  seconds,  then  "CLOSE"  again.  If 
closing is not possible after three attempts, the drive 
remains in this position.
In  addition,  the  drive  is  equipped  with  passive 
protection. The closing speed in closing range 2 and 
1 is reduced to 5 mm/s.

Significantly greater forces can be
exerted at the secondary closing edges.
Danger of crushing hands and fingers!

Summary of Contents for CDC 200/600

Page 1: ...t les kits de fixation Rogamos que pidan los juegos de fijaci n por separado de Originalbetriebsanleitung Seite 2 Anschluss Seite 14 Abmessungen Seite 16 Dimensi n en Original instructions Page 5 Conn...

Page 2: ...atisch der maximalen Druckkraft des Antriebes Drucklast N Hub 200N 150N 100N 50N 100 mm 200 mm 300 mm 400 mm SBD SBU Standard Drucklastdiagramm 600 mm Mindest Fl gelh he breite DieAngaben gelten f r n...

Page 3: ...e Kr fte auftreten Quetschgefahr im handzug nglichen Bereich Alle Kr fte ca 20 Abschaltreserve kurzzeitig Technische Daten Typ CDC 200 600 CDC 200 600 SBD Versorgung 24 VDC 15 1 0A 24 VDC 15 0 83A Ket...

Page 4: ...Maik Schmees Vorstand Prokurist Technischer Leiter 12 06 2010 Auf alle D H Artikel erhalten Sie 2 Jahre Garantie ab belegter bergabe der Anlage bis max 3 Jahre nach Auslieferungsdatum wenn die Montag...

Page 5: ...ain Maximum pressure load of chain is not automatically identical with maximum pressure force of the drive Pressure load diagram Scope of supply Drive unit with 2 5 m silicone cable Depending on the t...

Page 6: ...DAServicetool Running speed and forces Normal operation SHEV fast running CDC 200 600 200 N 200 N 6 7 mm s 11 4 mm s CDC 200 600 SBD 150 N 150 N 6 7 mm s 11 4 mm s 7 7 m m 6 7 m m s 2 0 0 N 5 m m s 1...

Page 7: ...ning agents or solvents Electrical devices accessories and packaging shouldbe sortedfor environmental friendlyrecycling Do not dispose electrical devices into household waste Only for EC countries Acc...

Page 8: ...pression N Course 200N 150N 100N 50N 100 mm 200 mm 300 mm 400 mm SBD SBU Standard Diagrammedechargedepression 600 mm Haut larg minimale du battant Les donn es s appliquent un montage non orientable d...

Page 9: ...0 200 N 200 N 6 7 mm s 11 4 mm s CDC 200 600 SBD 150 N 150 N 6 7 mm s 11 4 mm s Activit normale EFC fonctionnement rapide 7 7 m m 6 7 m m s 2 0 0 N 5 m m s 1 5 0 N 2 3 P l a g e s d e f e r m e t u r...

Page 10: ...intenance et nettoyage Nous accordons une garantie de 2 ans sur tous les articles D H dater de la r ception de l quipement documents l appui au maximum de 3 ans apr s la date de livraison condition qu...

Page 11: ...resi n m xima del motor Diagramadecargadecompresi n carga de compresi n N Carrera 200N 150N 100N 50N 100 mm 200 mm 300 mm 400 mm SBD SBU Est ndar 600 mm Altura latitud m nima de la hoja Las indicacion...

Page 12: ...amiento y fuerzas Servicio normal marcha r pida SVHC CDC 200 600 200 N 200 N 6 7 mm s 11 4 mm s CDC 200 600 SBD 150 N 150 N 6 7 mm s 11 4 mm s 7 7 m m 6 7 m m s 2 0 0 N 5 m m s 1 5 0 N 2 3 R a n g o d...

Page 13: ...H expira en el caso de conexi n de componentes de D H con otros equipos o cuando se mezclan los productos de D H con los de otros fabricantes Declaramos bajo nuestra responsabilidad que el producto de...

Page 14: ...un brown brun marr n BK schwarz black noir negro WH weiss white blanc blanco GY grau grey gris gris Mot b BN Mot a WH Nicht bei Not in case of Pas pour No en el caso GVL E K M Kabel gem D H Kabelverle...

Page 15: ...X a b LT Gruppe Group Groupe Grupo Mot a Mot b MOT BK BK OG 2x47kW En dm od ul Te rm ina l mo du le Mo du le ter mi na l EM 47 K WH BN OG YE WH BN OG YE Mot a Mot b HS TMS CDC 200 600 Mot a Mot b HS...

Page 16: ...dh partner com 2012 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Rights to technical modifications reserved Sous r serve de modifications techniques Derecho reservado a modificaciones...

Reviews: