Alarm 

CONDITION

 

On 

Off 

Off 

Off

 

Normal

 

Off 

On 

Off 

Beeps twice 
every 30 seconds

 

Utility Failure - 

The UPS is providing power to 

battery power-supplied outlets from its battery. 

Off 

On 

Off 

Rapid Beeping 
every 1/2 second

 

Utility  Failure  -

  The  UPS  is  providing  battery 

power.    Rapid  beeping  indicates  the  unit  will 
run out of power shortly. 

Off 

On 

On 

Constant tone

 

Battery  Overload  -

  Occurs  when  connected 

equipment  exceeds  the  listed  capacity  of  the 
UPS.    Turn  the  UPS  off,  unplug  at  least  one 
piece of equipment from battery outlets, wait 10 
seconds, reset the circuit breaker and turn the 
unit on. 

 

 

Problem

 

Possible Cause

 

Solution

 

Circuit breaker button is 
projecting from the side of 
the unit. 

Circuit breaker has tripped due 
to an overload. 

Turn the UPS off and unplug at least one 
piece of equipment.    Wait 10 seconds, reset 
the circuit breaker by depressing the button, 
and then turn the UPS on. 

The UPS does not perform 
expected runtime. 

Battery not fully charged. 

Recharge the battery by leaving the UPS 
plugged in. 

Battery is worn out. 

Contact CyberPower Systems about 
replacement batteries at 

[email protected]

 

The UPS will not turn on. 

The on/off switch is designed 
to prevent damage from rapidly 
turning it off and on. 

Turn the UPS off.    Wait 10 seconds and then 
turn the UPS on. 

The unit is not connected to an 
AC outlet. 

The unit must be connected to a 110/120V 
60Hz outlet. 

The battery is worn out. 

Contact CyberPower Systems about 
replacement batteries at 

[email protected]

 

Mechanical problem. 

Contact CyberPower Systems at 

[email protected]

 

PowerPanel

®

 Business 

Edition is inactive (all 
icons are gray). 

The USB / serial cable is not 
connected. 

Connect the USB / serial cable to the UPS 
unit and an open USB / serial port on the 
back of the computer.    You must use the 
cable that came with the unit. 

The USB / serial cable is 
connected to the wrong port. 

Check the back of the computer for an 
additional USB / serial port.    Move the cable 
to this port. 

The unit is not providing 
battery power. 

Shutdown your computer and turn the UPS 
off.    Wait 10 seconds and turn the UPS back 
on.    This should reset the unit. 

The serial cable is not the 
cable that came with the unit. 

Please use the serial cable that came with the 
unit for the software. 

Additional troubleshooting information can be found under “Support” at

 

www.CPSww.com

 

TROUBLESHOOTING 

DEFINITION FOR LCD ICONS & AUDIBLE INDICATION

 

 

Summary of Contents for OR1500PFCRT2U

Page 1: ...User s Manual OR1500PFCRT2U OR2200PFCRT2U OR2200PFCRT2Ua K01 0000206 00 ...

Page 2: ...f fire connect only to a circuit provided with 20 OR1500PFCRT2U and OR2200PFCRT2U or 30 OR2200PFCRT2Ua amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 CAUTION The UPS is suitable for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Processing Equipment ANSI NFPA 75 DO NOT USE FOR MEDIC...

Page 3: ...nt plugged into the outlet does not exceed the UPS unit s rated capacity 1500VA 900W for OR1500PFCRT2U 2000VA 1320W for OR2200PFCRT2U and 2200VA 1320W for OR2200PFCRT2Ua If the rated capacities of the unit are exceeded an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip 2 There are many factors that can affect the amount of power that your computer sy...

Page 4: ...three months to ensure battery life 8 To use PowerPanel Business Edition software connect the serial cable to the serial port or the USB port on both the UPS and the computer These OR units include one serial port and one USB port to allow connection and communication between the UPS and computers The primary computer with PowerPanel Business Edition installed is the computer that you will use to ...

Page 5: ...circuit breakers provide input optimal overload protection 9 USB Port The USB port allows connection and communication between the USB port on the computer and the UPS unit 10 Communication Protection Ports Communication protection ports will protect any standard modem fax telephone line network or Ethernet connection RJ11 RJ45 11 Wiring Fault Indicator red This LED indicator will illuminate to wa...

Page 6: ...nergy conducted through these materials could cause severe burns 3 CAUTION Do not dispose of batteries in a fire The batteries may explode 4 CAUTION Do not open or mutilate batteries Released material is harmful to the skin and eyes It may be toxic CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS BATTERY REPLACEMENT PROC...

Page 7: ...until the battery reaches low capacity 8 OVER LOAD icon This icon appears and an alarm sounds to indicate the battery supplied outlets are overloaded To clear the overload unplug some of your equipment from the battery supplied outlets until the icon turns off and the alarm stops 9 FAULT icon This icon appears if there is a problem with the UPS Contact CyberPower Systems at tech cyberpowersystems ...

Page 8: ...Medium 88 139Vac This is the default setting High 90 136Vac This unit is most sensitive to voltage fluctuations LCD Always On On The LCD is always on whether or not the LCD button is pressed Off In Line Mode if the LCD display button is not touched for 1 minute the UPS will enter Sleeping Mode The LCD will not appear until the display button is pressed In Battery Mode the LCD is always on Self Tes...

Page 9: ...cyberpowersystems com The UPS will not turn on The on off switch is designed to prevent damage from rapidly turning it off and on Turn the UPS off Wait 10 seconds and then turn the UPS on The unit is not connected to an AC outlet The unit must be connected to a 110 120V 60Hz outlet The battery is worn out Contact CyberPower Systems about replacement batteries at tech cyberpowersystems com Mechanic...

Page 10: ...ating Relative Humidity 0 to 90 non condensing Size L x W x H 433 x 388 x 88 mm 2U Rack 17 x 15 3 x 3 5 Net Weight 55 1lbs 25kg 59 3lbs 26 9kg 60lbs 27 2kg Battery Type 12V 7Ah RBP433 CyberPower 12V 8 5Ah RBP435 CyberPower 12V 8 5Ah RBP435 CyberPower Typical Battery Recharge Time 8 hours from total discharge Typical Battery Life 3 to 6 years depending on number of discharge recharge cycles Recomme...

Page 11: ...nty Cover This warranty covers defects in materials and workmanship in the Product under normal use and conditions It also covers equipment that was connected to the Product and damaged because of the failure of the Product What is the Period of Coverage This warranty covers the Product for three years and connected equipment for as long as you own the Product Who Is Covered This warranty only cov...

Page 12: ... improper operation or maintenance or use with items not designed or intended for use with the Product such as laser printers appliances aquariums medical or life support devices etc What are the Limitations The sole and exclusive remedies of the Initial Customer are those provided by this Warranty 1 This Warranty does not apply unless the Product and the equipment that was connected to it were co...

Page 13: ...ct is not for use in high risk activities or with aquariums The Product is not designed or intended for use in hazardous environments requiring fail safe performance or for use in any circumstance in which the failure of the Product could lead directly to death personal injury or severe physical or property damage or that would affect operation or safety of any medical or life support device colle...

Reviews: