REPLACING THE BATTERY
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
CAUTION!
Servicing of the battery should only be performed by trained personnel familiar with batteries and their
precautions. For more information on battery replacement, contact your dealer or call the number on
this manual.
Replacement of batteries located in an
OPERATOR ACCESS AREA
.
1. When replacing batteries, replace with the same number of the following battery: CyberPower RBP433 for
the OR1500PFCRT2U; CyberPower RBP435 for the OR2200PFCRT2U and OR2200PFCRT2Ua.
2.
CAUTION!
Risk of Energy Hazard, 12 V, maximum 7(for the OR1500PFCRT2U) or 8.5 (for the
OR2200PFCRT2U and OR2200PFCRT2Ua) Ampere-hour battery. Before replacing batteries, remove
conductive jewelry such as chains, wrist watches, and rings. High energy conducted through these
materials could cause severe burns;
3.
CAUTION!
Do not dispose of batteries in a fire. The batteries may explode;
4.
CAUTION!
Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may
be toxic.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF
USED BATTERIES ACCORDING TO LOCAL REGULATIONS.
BATTERY REPLACEMENT PROCEDURE:
REMINDER:
Batteries are considered
HAZARDOUS WASTE
and must be disposed of properly. Most
retailers that sell lead-acid batteries collect used batteries for recycling, as required by local regulations.
BATTERY REPLACEMENT
Remove the right side front panel.
Remove the three retaining screws of
the cable protection cover then
remove the cover.
Disconnect the black and red cable.
Remove the four retaining screws.
Insert the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
sequence of above steps. Recharge the unit for 4-8 hours to ensure the UPS performs
expected runtime.