CyberPower OR1500PFCRT2U User Manual Download Page 7

 
1.  INPUT voltage meter:

 This meter measures the AC voltage that the UPS 

system is receiving from the utility wall outlet. The UPS is designed,   
through the use of automatic voltage regulation, to continuously correct   
output voltage to connected equipment to a safe 110/120 voltage output   
range. In the event of a complete power loss, severe brownout, or   
over-voltage, the UPS relies on its internal battery to supply consistent   
110/120 output voltage. The INPUT voltage meter can be used as a   
diagnostic tool to identify poor-quality input power. 

2.  OUTPUT voltage meter: 

This meter measures, in real time, the AC   

voltage that the UPS system is providing to the computer, such as   
normal line mode, AVR mode, and battery backup mode. (Note: The   
OUTPUT voltage meter shows the status of the battery backup outlets.) 

3.  ESTIMATED RUN TIME:

 This displays the run time estimate of the UPS with current battery capacity and 

load. 

4.  NORMAL icon: 

This icon appears when the UPS is working under normal conditions. 

5.  BATTERY icon: 

During a severe brownout or blackout, this icon appears and an alarm sounds (two short 

beeps followed by a pause) to indicate the UPS is operating from its internal batteries. During a prolonged 
brownout or blackout, the alarm will beep rapidly every 1/2 second (and the BATT.CAPACITY meter shows 
one 20% capacity segment shaded. The capacity depends on how much load added and the runtime left. 
You can setup the Low Battery Threshold through PowerPanel

®

 Business Edition software.) to indicate the 

UPS’s batteries are nearly out of power. You should save files and turn off your equipment immediately or 
allow the software to shut the system down. 

6.  AVR (Automatic Voltage Regulation) icon: 

This icon appears whenever your UPS is automatically 

correcting low AC line voltage without using battery power. This is a normal, automatic operation of your 
UPS, and no action is required on your part. 

7.  SILENT MODE icon: 

This icon appears whenever the UPS is in silent mode. The buzzer does not beep 

during silent mode until the battery reaches low capacity. 

8.  OVER LOAD icon: 

This icon appears and an alarm sounds to indicate the battery-supplied outlets are 

overloaded. To clear the overload, unplug some of your equipment from the battery-supplied outlets until 
the icon turns off and the alarm stops. 

9.  FAULT icon: 

This icon appears if there is a problem with the UPS, Contact CyberPower Systems at 

[email protected]

 for further help and support.   

F01: Battery Mode or Line Mode Overload fault 
F02: Battery Output Short fault 
F03: Charger Fault 
F04: Internal Fault 

10.  BATT. CAPACITY meter: 

This meter displays the approximate charge level (in 20% increments) of the 

UPS’s internal battery. During a blackout or severe brownout, the UPS switches to battery power, the 
BATTERY icon appears, and the charge level decreases. 

11.  LOAD CAPACITY meter: 

This meter displays the approximate output load level (in 20% increments) of 

the UPS battery outlets. 

 

Advanced LCD Functions Setup 

There are advanced LCD functions that can be setup through LCD Display button. (1) 

Mute

: Enable or disable 

any audible alarm caused by an event. (2) 

Sensitivity

: Control the sensitivity of the UPS to switch to Battery 

Mode by selecting UPS shutdown voltage range. The higher the sensitivity, the easier the UPS will switch to 
Battery Mode. (3) 

LCD Always On

: Keep the LCD always lit. (4) 

Self Test

: Perform a test in Line Mode to test 

Battery Mode function. It will return to Line Mode after the test is completed. (5) 

ESC

: Leave setup mode 

without changing any settings and return to LCD status display screen. 
For the 

Mute 

function, press Display button for 2 seconds to enable or disable audible alarm. When   

you enable audible alarm, the Silent icon is not lit. When you disable audible alarm, the Silent icon is lit. 
For the 

Sensitivity

,

 LCD Always On

Self Test

, and

 ESC

 functions, press Display button for 8 seconds to 

enter 

Function Setup 

screen. Press Display button once to choose between Sensitivity, LCD Always On, Self 

Test, and ESC Functions. When the function is chosen, press 2 seconds to enter 

Mode Setup 

screen. (or If the 

function you select is ESC, press 2 seconds and you will leave the Function Setup screen and return to LCD 

DEFINITION FOR ILLUMINATED LCD INDICATORS

 

 

 

 

Summary of Contents for OR1500PFCRT2U

Page 1: ...User s Manual OR1500PFCRT2U OR2200PFCRT2U OR2200PFCRT2Ua K01 0000206 00 ...

Page 2: ...f fire connect only to a circuit provided with 20 OR1500PFCRT2U and OR2200PFCRT2U or 30 OR2200PFCRT2Ua amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 CAUTION The UPS is suitable for use in a computer room as defined in the Standard for the Protection of Electronic Computer Data Processing Equipment ANSI NFPA 75 DO NOT USE FOR MEDIC...

Page 3: ...nt plugged into the outlet does not exceed the UPS unit s rated capacity 1500VA 900W for OR1500PFCRT2U 2000VA 1320W for OR2200PFCRT2U and 2200VA 1320W for OR2200PFCRT2Ua If the rated capacities of the unit are exceeded an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip 2 There are many factors that can affect the amount of power that your computer sy...

Page 4: ...three months to ensure battery life 8 To use PowerPanel Business Edition software connect the serial cable to the serial port or the USB port on both the UPS and the computer These OR units include one serial port and one USB port to allow connection and communication between the UPS and computers The primary computer with PowerPanel Business Edition installed is the computer that you will use to ...

Page 5: ...circuit breakers provide input optimal overload protection 9 USB Port The USB port allows connection and communication between the USB port on the computer and the UPS unit 10 Communication Protection Ports Communication protection ports will protect any standard modem fax telephone line network or Ethernet connection RJ11 RJ45 11 Wiring Fault Indicator red This LED indicator will illuminate to wa...

Page 6: ...nergy conducted through these materials could cause severe burns 3 CAUTION Do not dispose of batteries in a fire The batteries may explode 4 CAUTION Do not open or mutilate batteries Released material is harmful to the skin and eyes It may be toxic CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS BATTERY REPLACEMENT PROC...

Page 7: ...until the battery reaches low capacity 8 OVER LOAD icon This icon appears and an alarm sounds to indicate the battery supplied outlets are overloaded To clear the overload unplug some of your equipment from the battery supplied outlets until the icon turns off and the alarm stops 9 FAULT icon This icon appears if there is a problem with the UPS Contact CyberPower Systems at tech cyberpowersystems ...

Page 8: ...Medium 88 139Vac This is the default setting High 90 136Vac This unit is most sensitive to voltage fluctuations LCD Always On On The LCD is always on whether or not the LCD button is pressed Off In Line Mode if the LCD display button is not touched for 1 minute the UPS will enter Sleeping Mode The LCD will not appear until the display button is pressed In Battery Mode the LCD is always on Self Tes...

Page 9: ...cyberpowersystems com The UPS will not turn on The on off switch is designed to prevent damage from rapidly turning it off and on Turn the UPS off Wait 10 seconds and then turn the UPS on The unit is not connected to an AC outlet The unit must be connected to a 110 120V 60Hz outlet The battery is worn out Contact CyberPower Systems about replacement batteries at tech cyberpowersystems com Mechanic...

Page 10: ...ating Relative Humidity 0 to 90 non condensing Size L x W x H 433 x 388 x 88 mm 2U Rack 17 x 15 3 x 3 5 Net Weight 55 1lbs 25kg 59 3lbs 26 9kg 60lbs 27 2kg Battery Type 12V 7Ah RBP433 CyberPower 12V 8 5Ah RBP435 CyberPower 12V 8 5Ah RBP435 CyberPower Typical Battery Recharge Time 8 hours from total discharge Typical Battery Life 3 to 6 years depending on number of discharge recharge cycles Recomme...

Page 11: ...nty Cover This warranty covers defects in materials and workmanship in the Product under normal use and conditions It also covers equipment that was connected to the Product and damaged because of the failure of the Product What is the Period of Coverage This warranty covers the Product for three years and connected equipment for as long as you own the Product Who Is Covered This warranty only cov...

Page 12: ... improper operation or maintenance or use with items not designed or intended for use with the Product such as laser printers appliances aquariums medical or life support devices etc What are the Limitations The sole and exclusive remedies of the Initial Customer are those provided by this Warranty 1 This Warranty does not apply unless the Product and the equipment that was connected to it were co...

Page 13: ...ct is not for use in high risk activities or with aquariums The Product is not designed or intended for use in hazardous environments requiring fail safe performance or for use in any circumstance in which the failure of the Product could lead directly to death personal injury or severe physical or property damage or that would affect operation or safety of any medical or life support device colle...

Reviews: