Copyright © 2012 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
12
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [208V] [220V] [230V] [240V]
230V
Output Frequency
= [50Hz][60Hz]
50Hz
ECO Mode *
[0%] (Disable) [10%][15%] (Enable)
0%
Bypass Mode **
[DIS] (Disable) [ENA] (Enable)
Enable
Converter Mode
[DIS] (Disable) [ENA] (Enable)
Disable
EPO/ROO***
[EPo] [Roo]
EPO
EBM Number****
[0bP]/[1bP]/[2bP]/[3bP]/[4bP]/[5bP]/[6bP]/[7bP]/[8bP]/[9bP]
/[AbP]
0(for
–E models) / 1 (for –EXL models)
Bypass when UPS
is Off
[F1d](Disable) [F1E](Enable)
Disable
*) This function would be set as 0% when Converter Mode is enabled.
icon is lighting during setting ECO mode.
**) UPS has no bypass when Converter Mode is enabled.
icon is lighting during setting bypass mode.
*** ROO (Remote On/Off): If ROO is enabled, UPS can be turn on/off by the ROO port. If ROO port is disconnected, UPS
will be turned off. If ROO port is connected, UPS will be turned on when the utility is normal
****) 1. UPS cannot detect the numbers of external battery automatically, so manual input from user is necessary.
2. For
–E models, the maximum number is 3. Option [AbP] means 10.
SILENCING AUDIBLE ALARMS
Press
the “
ENTER
” button on simultaneously for 5 seconds to disable or enable the alarm system while in battery mode.
Note: Some audible alarms (Over
Temperature, Fan Fail, etc.) can’t be silenced.
MANUAL BATTERY TEST
Press
the “
ENTER
” button simultaneously for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or
converter mode.