BASIC OPERATION

 

 

 

10

 

 

REPLACE: 

This  icon  appears  if  the  batteries  need  to  be 

replaced. 

 

 

Event ID Descriptions

 

Event ID 

Description of Cause 

Bus Start Fail: 

DC-DC converter or bus sensing circuit failed. 

Bus Volt High:

 DC-DC converter failed. 

Bus Volt Low: 

DC-DC converter failed. 

Bus Unbalanced: 

DC-DC converter failed. 

INV Start Fail: 

Inverter circuit failed. 

INV  Volt  High:

  Inverter  circuit  or  output  voltage  sensing 

circuit failed. 

INV Volt Low:

 The load may be too heavy or inverter circuit 

failed. 

INV Short: 

The inverter circuit failed. 

Bat Volt  High:

  The  external  battery  module  connection  is 

wrong, or the charger failed. 

10 

Bat Volt Low: 

Batteries failed. 

11 

Over  Temperature:

  High  ambient  temperature,  or  the 

ventilation hole has been covered. 

12 

Over Load: 

UPS is overloaded. 

54 

High  Temperature:

  High  ambient  temperature,  or  the 

ventilation hole  has  been  covered.  This is shown  only  when 
start up UPS. 

 

55 

Bat Low: 

Battery voltage is too low to DC start UPS.

 

57 

EPO Off:

 Missing the EPO connection

 

58 

Fan Fail: 

The ventilation hole has been covered, or the fans 

can’t work.

 

59 

Bat Bad: 

Battery failed.

 

 

BUTTON OPERATION

 

Button 

Operation Description 

ON 

Press this button to turn on UPS. 

OFF 

Press this button to turn off UPS.* 

ENTER/

▲ 

Press this button to scroll up in the LCD menu. 
Press  this  button  simultaneously  for  5  seconds  to  disable  or 
enable the alarm system while in battery mode. 
Press this button simultaneously for 5 seconds to enter UPS 
self-testing while in AC mode, ECO mode, or converter mode. 
In  setting  mode,  press  this  button  to  confirm  selection,  or 
press this button for long time to exit setting mode and saving 
changes. 

ESC/

▼ 

Press this button to scroll down in the LCD menu. 
Press this button for long time to get into setting mode 
In setting mode, press this button to display next selection, or 
press  this  button  for  long  time  to  exit  setting  mode  without 
saving changes. 

ENTER/

▲ + ESC/▼ 

Switch  to  bypass  mode:  When  the  main  power  is  normal, 
press  these  two  buttons  simultaneously  for  5  seconds,  then 
UPS will enter to bypass mode. 

*) If utility power is connected

UPS will keep charging but cut off output. 

Summary of Contents for OLS5200E

Page 1: ...User s Manual OLS5200E EXL CyberPower Systems Inc www cyberpower com K01 C000106 01 ...

Page 2: ...tallations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipme...

Page 3: ...Copyright 2012 CyberPower Systems Inc UNPACKING 2 UPS User s manual Phone line USB communication cable PowerPanel Business Edition software CD Strap tie ...

Page 4: ...quipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to the technical specifications 6 This UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically charge even when the unit is switched off 7 To maintain an optimal battery charge leave the UPS plugged into an AC outlet at all times ...

Page 5: ...e UPS and alter its various programmable parameters 7 USB port This is a connectivity port which allows communication and control between the UPS and the connected computer It is recommended to install the PowerPanel Business Edition Agent software on the PC Server connected with the USB cord 8 Surge Protected Communication Ports RJ 45 RJ 11 These ports are used to protect standard RJ 45 RJ 11 bas...

Page 6: ...tor to daisy chain the next Battery module Remove the connector cover for access 2 On board Replaceable Fuse Cover Replaceable fuse is accessible from the rear panel It must be done by qualified personnel 3 Output Connector Use this output Connector to connect the Battery module to the Power module or to the next Battery module BPSE120V45A ...

Page 7: ... Step 1 Loosen the M3 screws to remove the metal covers of the AC input and output terminal blocks as photograph 1 Step 2 Connect the AC power to input terminal block and the load to output terminal block The line neutral and ground must be connected correctly Then use the cable ties to fix the AC wires to rings below the terminal blocks as photograph 2 Step 3 Tighten the metal covers with M3 scre...

Page 8: ...MODULE Step 1 Loosen the two screws to remove the battery cable retention bracket of the power module Step 2 Use the battery cable of the Battery module to connect the Battery module to the Power module Step 3 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable ...

Page 9: ...ery module to the Power module using battery cable Step 2 Loosen the two screws to remove the battery cable retention bracket of the 1 st battery module Step 3 Use the battery cable to connect the 2 nd Battery module to the 1 st Battery module Step 4 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable ...

Page 10: ...capacity This meter displays the approximate charge level in 20 increments of the UPS s internal battery During a blackout or severe brownout the UPS switches to battery power the BATTERY icon appears and the charge level decreases MUTE This icon appears whenever the UPS is in silent mode The alarm does not beep during silent mode until the battery reaches low capacity SCHEDULE Users can setup the...

Page 11: ... is too low to DC start UPS 57 EPO Off Missing the EPO connection 58 Fan Fail The ventilation hole has been covered or the fans can t work 59 Bat Bad Battery failed BUTTON OPERATION Button Operation Description ON Press this button to turn on UPS OFF Press this button to turn off UPS ENTER Press this button to scroll up in the LCD menu Press this button simultaneously for 5 seconds to disable or e...

Page 12: ...WN XX X Min Hr Displays the Time Delay to Shutdown UPS TIME TO TURN ON XX X Min Hr Displays the Time Delay to Restart UPS LCD SETTINGS CONFIGURATION There are 8 UPS settings that can be configured by the user 1 Press the ESC button simultaneously for 5 seconds to activate the setting mode The first configuration parameter will be displayed on the LCD screen Note The manual settings programming mod...

Page 13: ...when Converter Mode is enabled icon is lighting during setting bypass mode ROO Remote On Off If ROO is enabled UPS can be turn on off by the ROO port If ROO port is disconnected UPS will be turned off If ROO port is connected UPS will be turned on when the utility is normal 1 UPS cannot detect the numbers of external battery automatically so manual input from user is necessary 2 For E models the m...

Page 14: ...ins wrist watches and rings CAUTION Do not open or mutilate the batteries Electrolyte fluid is harmful to the skin eyes and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please ref...

Page 15: ...ne Network Protection RJ11 RJ45 One In One Out Overload Protection Line Mode 105 110 Overload warning only No shutdown 110 120 Warning transfer to bypass after 60s 120 Transfer to bypass immediately Battery Mode 105 110 Overload warning only No shutdown 110 120 Warning shutdown after 10s 120 Shutdown immediately Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker ...

Page 16: ...range for output frequency 1 2 3 4 5 6 7 8 9 10 When input frequency is out of synchronization window but within 40 70Hz UPS can stay in line mode and output frequency is regulated at 50 60Hz 0 5 with load derating by 40 Software Power Management Software PowerPanel Business Edition Physical Dimensions W H D 7 72 x 13 28 x 16 38 in 196 337 416 mm Net Weight 62 2 27 8lbs 28 2 12 6Kg ...

Page 17: ...n UPS and turn off AC input 2 Contact CyberPower for repair EPO OFF Missing the EPO connection Check the EPO connection Fault Over Temperature High ambient temperature 1 Shut down UPS Restart UPS to Check the fan for operation and if the ventilation hole has been covered 2 Contact CyberPower for repair Output Short Output short circuit 1 Shut down UPS 2 Your attached equipment may have problems pl...

Reviews: