4

RACKMOUNT INSTALLATION FOR 4-POST RACK

To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.

Step 1: Remove the dust covers

Remove five dust covers from the screw holes as shown below.

Step 2: Rackmount ear & hanging bracket installation

Attach two rack mount ears to the step-down transformer using eight black M5X7L flat head screws. Install 
hanging brackets using six silver M5X6L pan head screws. 

Step 3: Rackmount rail Installation

The rails adjust to mount in 19 in (48 cm) racks from 20.5 in to 36 in (52 cm to 91.5 cm) deep. Select the 
proper holes in the rack for positioning the step-down transformer in the rack. The step-down transformer 
takes up 2 rack units: rack hole positions 1 through 6.

Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily 
support the rails in place. 

Step 4: Adjust rackmount rails to fit your rack

Adjust the rail depth to match your rack depth. Attach the rackmount rail to your rack with two black 
M5X6L pan head screws and two plastic washers at the front of the rack (square holes 1 and 4 as shown 
below). Secure the rail to the rear of the rack with two black M5X12L screws and two plastic washers.

HARDWARE INSTALLATION

1

2

Caution: Important Instructions

Summary of Contents for OL10KSTF

Page 1: ...se read this manual and follow the instructions for installation and operation 201 Cyber Power Systems Inc All rights reserve K01 0000755 01 INSTALLATION AND OPERATION MANUAL SMART APP ONLINE STEP DOWN TRANSFORMER OL6KSTF OL10KSTF ...

Page 2: ... OL6KSTF and OL10KSTF step down transformer models that are covered in this manual are intended for installation in an environment within 32 F to 104 F 0 C to 40 C free of conductive contaminants SPECIAL SYMBOLS Warning High voltage Risk of Electric Shock Caution Important Instructions must always be followed Do Not Discard the UPS or UPS batteries in trash The batteries contain lead acid For more...

Page 3: ...aminants Do not install this step down transformer where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range Never install a step down transformer or associated wiring or equipment during a lightning storm Do not work alone under hazardous conditions Input circuit breaker must be OFF during the building installation Only qualified maintenan...

Page 4: ...ire prior to connecting the line wires Connect the Protection Earth PE safety conductor before any other cables are connected SAFETY INSTRUCTIONS CONT PERSONAL SAFETY CONT RISK OF ELECTRIC SHOCK The step down transformer should be placed near the connected equipment and easily accessible All step down transformer models covered in this document are permanently connected equipment and only qualifie...

Page 5: ... 1 Whats In The Box 2 OVERVIEW 3 Step Down Transformer HARDWARE INSTALLATION Rackmount Installation For 4 Post Rack Rackmount Installation For 2 Post Rack Vertical Tower Installation ELECTRICAL INSTALLATION Hardwiring the Input Output Terminals 8 Connecting a Step Down Transformer to a UPS Power Module TECHNICAL SPECIFICATIONS PRODUCT REGISTRATION LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE...

Page 6: ...he step down transformer converts voltage from 200 240V down to 100 120V UNPACKING PROCEDURES The UPS system is very heavy please handle with care Wear safety shoes and use a hydraulic equipment lift if one is available At least two people are required for all handling operations including unpacking lifting and installation in a rack system Do not use the lifting straps to carry the unit around th...

Page 7: ...WIRE ROJ REMOVE OUTER JACKET POWER CABLE L630PHW6FT INCLUDED WITH OL6KSTF x1 3 FT 10 3 AWG CONDUCTOR WIRE ROJ REMOVE OUTER JACKET WITH CONDUIT 6AWGHW3FT INCLUDED WITH OL10KSTF x1 TERMINAL BLOCK CABLE GLANDS x2 LEFT RIGHT HANGING BRACKETS x1 LEFT RIGHT RACKMOUNT RAILS x1 INPUT OUTPUT TERMINAL BLOCK COVER x1 2U RACK MOUNT EARS TOWER STANDS x2 TOWER INSTALLATION TIE PLATE x1 BLACK M5X7L FLAT HEAD SCR...

Page 8: ...nput Circuit Breaker Provides input overload and fault protection 2 Input Output Terminal Block Connect to input power source output to equipment load 3 6x NEMA 5 20R Outlets 120Vac Output receptacles to connect equipment load 4 Output Circuit Breaker 120Vac Provides output overload and fault protection FRONT OL6KSTF OL10KSTF BACK OL6KSTF OL10KSTF 1 2 3 4 ...

Page 9: ...on The rails adjust to mount in 19 in 48 cm racks from 20 5 in to 36 in 52 cm to 91 5 cm deep Select the proper holes in the rack for positioning the step down transformer in the rack The step down transformer takes up 2 rack units rack hole positions 1 through 6 Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily support the rails in place S...

Page 10: ... the rack with the front of the unit facing toward you Secure the step down transformer to your rack with four black M5X12L pan head screws at the front of the rack square holes 1 and 4 as shown above NOTE To slide the step down transformer out from the rack The step down transformer will be secured by a safety locking mechanism midway of pulling it out of the rack Use both hands to hold the step ...

Page 11: ...erved All other trademarks are the property of their respective owners 6 HARDWARE INSTALLATION CONT RACKMOUNT INSTALLATION FOR 2 POST RACK Step 1 Remove side dust covers Remove five dust covers from screw holes as shown below Step 2 Rackmount ears installation Attach the included rackmount ears to the center holes on the sides of the UPS using eight black M5X7L screws as shown below Step 3 Secure ...

Page 12: ...mer on its side with the rubber pads facing down Install dust covers on open screw holes If installing the step down transformer together with a UPS and Extended Battery Module EBM secure the tie plate between the UPS EBM and the step down transformer using four black M5X7L flat head screws Optionally adhere four circular rubber pads to each rack mount ear to use as tower stands and screw them on ...

Page 13: ...the two screws to secure the bottom cover on to the step down transformer terminal block Step 3 Input Output configuration Insert the input output cables through the appropriate cable gland Hardwire the input output wiring to their respective terminals as shown in the terminal block identification and configuration table Step 4 Secure the top cover Use four screws to secure the top terminal block ...

Page 14: ...0 Vac L1 N L2 100 Vac 0 100 Vac L1 L2 200 Vac L1 L2 220 Vac L1 N L2 110 Vac 0 110 Vac L1 L2 220 Vac L1 L2 230 Vac L1 N L2 115 Vac 0 115 Vac L1 L2 230 Vac INPUT VOLTAGE AC OUTPUT CONNECTION OUTPUT VOLTAGE L1T L2 208 Vac L1 N L2 120 Vac 0 120 Vac L1 L2 240 Vac L1 L2T 208 Vac INPUT VOLTAGE AC OUTPUT CONNECTION OUTPUT VOLTAGE L1 L2 240 Vac L1 N L2 120 Vac 0 120 Vac L1 L2 240 Vac L1 L2T 208 Vac 240V AC...

Page 15: ...spective owners 10 CONNECTING A STEP DOWN TRANSFORMER TO A UPS POWER MODULE The following illustrations provide the recommended connections between a step down transformer and a CyberPower Smart App Online UPS System ELECTRICAL INSTALLATION CONT OL6KRTF OL8KRTF OL10KRTF OL6KRTMBTF OL8KRTMBTF OL10KRTMBTF ...

Page 16: ...ions L x W x H 23 6 x 17 x 3 46in 60 x 43 3 x 8 8cm Net Weight 95 5 lb 43 4 kg 119 7 lb 54 4 kg ENVIRONMENTAL Operating Temperature 32 F to 104 F 0 C to 40 C Operating Relative Humidity 0 to 90 Non condensing SAFETY Conformance Approvals UL 200V are derated by 20 208 V are derated by 10 for OL10KSTF CyberPower requests that you complete and return the Warranty Registration Card enclosed with the P...

Page 17: ...rranty Cover This warranty covers defects in materials and workmanship in the Product under normal use and conditions It also covers equipment that was connected to the Product and damaged because of the failure of the Product What is the Period of Coverage This warranty covers the Product for three years and connected equipment for as long as you own the Product Who Is Covered This warranty only ...

Page 18: ... damage to your connected equipment 4 Pack and ship the product to CyberPower and if requested the item s of Connected Equipment a repair cost estimate for the damage to the Connected Equipment and all claim forms that CyberPower provides to you Show the Claim Number on the shipping label or include it with the product You must prepay all shipping costs you are responsible for packaging and shipme...

Page 19: ...hion with any extension cords another Product or device similar to the Product surge suppressor or power tap Any such installation voids the Limited Warranty 3 The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license instruction manual or warnings provided with the Product and the equipment connected to it 4 The...

Page 20: ...e limitation may not apply to you 6 The Product is not for use in high risk activities or with aquariums The Product is not designed or intended for use in hazardous environments requiring fail safe performance or for use in any circumstance in which the failure of the Product could lead directly to death personal injury or severe device collectively High Risk Activities CyberPower expressly discl...

Page 21: ...erves the right to change or correct the contents and does not assume any responsibility for omissions or errors Need Additional Help Feel free to contact our Tech Support department with installation troubleshooting or general product questions CyberPower Technical Support Phone 1 877 297 6937 Email tech cpsww com Web www CyberPowerSystems com Address 4241 12th Avenue E Suite 400 Shakopee MN 5537...

Page 22: ...erSystems com For USA and Canada 4241 12th Ave East Suite 400 Shakopee MN 55379 Toll free 877 297 6937 For all other regions Please visit our website for local contact information Copyright 2019 Cyber Power Systems Inc All rights reserved ...

Reviews: