TECHNICAL SPECIFICATIONS
MODELS
OL6KRT
OL8KRT
OL10KRT
CONFIGURATION
Capacity (VA)
6000 VA*
8000 VA
10000 VA
Capacity (Watts)
5400 W*
8000 W
10000 W
Form Factor
Rackmount/Tower
Energy-saving
Technology
INPUT
Input Voltage Range
200~240 V
Input Frequency Range
40~70 Hz (auto-sensing)
Input Power Factor
0.99
Cold Start
Yes
OUTPUT
Output Waveform
Sine wave
Output Voltage
200, 208, 220, 230, 240 V ±2% (Configurable)
Output Frequency
50/60 Hz ±0.25 Hz (Auto-Sensing or Configurable)
Transfer Time (Typical)
0ms
Rated Power Factor
0.9
1
1
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load
Crest Factor
3 : 1
ECO Mode Bypass
Voltage Range
±10%, ±15% (Configurable)
UPS Outlets
(2) L6-20R, (2) L6-30R | (3) L6-30R, (1) Terminal block
PROTECTION
Surge Protection
IEC 61000-4-5 Level 3 (2430 Joules)
Phone / Network Surge
Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode: 105~125% Load for 1 min, 126~150% Load for 10 sec
Battery Mode: 105~130% Load for 10 sec, 131~150% Load for 2 sec
Short Circuit Protection
BATTERY
Specifications
(20) 12 V/7 Ah
(20) 12 V/9 Ah
Recharge Time 0-90%
(Typical)
4 hours
5 hours
*OL6KRT output power will be derated base on input voltage as following
VA
Watts
6,000 (6 kVA) at 220, 230, 240 V input
5,400 (5.4 kVA) at 208 V input
4,800 (4.8 kVA) at 200 V input
5,400 (5.4 kW) at 220, 230, 240 V input
4,860 (4.86 kW) at 208 V input
4,320 (4.32 kW) at 200 V input