LCD Configuration Settings Cont.
Silencing Audible Alarms
1. Press any of the four function buttons on the LCD control panel.
Note:
Battery Low
” condition. This condition will still result in an
audible alarm.
2. Change the “
Audible Alarms
” option to “
Disable
” in the LCD control panel and it will no longer give an
audible alarm for any malfunction.
CONFIGURE
SUBMENU
AVAILABLE SETTINGS
DEFAULT SETTING
Charger Check
[Disable] [Enable]
Set [Disable] or [Enable] to constantly monitor the charger function.
Disable
With Transformer
[Disable] [Enable]
Set [Enable] when UPS is installed with a step-down transformer.
Disable
Backfeed Check
[Disable] [Enable]
Set [Enable] to activate backfeed connector function.
Disable
Reset ReplaceBAT [Activate?]
Manually reset the Battery Replacement date.
None
Reset Load Energy
[Activate?]
Reset Load Energy Consumption (KWH) value.
None
USING THE UPS SYSTEM CONT.
Signal Inputs
Disable
[Disable] [EPO] [ROO][Manual Bypass]
Set [EPO] (Emergency Power Off) to shut down the UPS remotely
when the contact is open.
Set [ROO] (Remote On/Off) to turn the UPS on remotely when
the contact is closed and turn the UPS off remotely
when the contact is open. The On/Off power button on the front
panel will be disabled when set to [ROO].
Set [Manual Bypass] to use Maintenance Bypass PDU (MBP).
Please refer to the MBP user manual for correct operating procedures.
If you don't have install MBP , please don't set Signal Inputs to
[Manual Bypass].
[Mode:DHCP] [Mode:Manual]
Mode:DHCP
IP Address
None
[IP Address] [Subnet Mask] [Gateway] (for [Mode:Manual])
Select [Mode:Manual] to set [IP Address] [Subnet Mask]
[Gateway] on the network card (RMCARD) or select DHCP to
retrieve IP address settings from the local network DHCP server.
1
This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
2
UPS has no bypass when Generator Mode is enabled.
3
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
4
The Low Battery threshold setting will only affect the warning of Power Management Software (PowerPanel® Business) and RMCARD interface.
5
If function is disabled, the Smart Battery Management (SBM) carries out battery tests when certain operating conditions are met.
LowBat Capacity
4
Threshold= [20%][25%] [30%][35%]……[55%][60%][65%]
20%
LowBat Runtime
4
Threshold= [0min][1min][2min][3min]..….[29min][30min]
5min
[Disable
5
][1 Weeks][2 Weeks] [3 Weeks] [4 Weeks]
Period Battery Test
Disable