LCD Configuration Settings Cont.
CONFIGURE
SUBMENU
AVAILABLE SETTINGS
DEFAULT SETTING
Language
[English] [Español-Spanish] [Français-French]
[Deutsch-German]
User can select the desired LCD control panel language.
English
Generator Mode
2
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring to
Battery Mode when set to [Enable].
Disable
Communication
[Disable] [Enable]
All communication ports on the UPS are
[Disable] or [Enable].
Enable
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
Select what UPS events will trigger real potential-free
dry contacts for industrial control.
I/P Power Fail
Converter Mode
3
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Sets [O/P Freq = 50Hz] or [O/P Freq = 60Hz]
to convert the input frequency to the required
output frequency.
Converter OFF
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
Sets the amount of time the LCD screen stays on
after no user input. The [Disable] option keeps the
LCD screen on at all times.
5 minutes
Clear Event Log
[Activate?]
Clears all the events stored in the LCD control panel
Event Log.
None
Button OFF LOCK
[Disable] [Enable]
To prevent accidental UPS power ON/OFF button
operation set to [Enable]. The Power ON/OFF button
will be locked and will not function.
Disable
Charger Function
[SBM] [Constant]
Set [SBM] to activate Smart Battery Management
to charge the batteries.
Set [Constant] to use trickle charge method to
charge the batteries.
SBM
USING THE UPS SYSTEM CONT.