Code setting table
22
Code table number
2
3
4
5
Code
VDE-AR-N4105
VDE0126-1-1
VDE0126-1-1/UTE VDE0126-1-1/TW
Default
Setting
Trip time
Setting
Trip time
Setting
Trip time
Setting
Trip time
Start up time
60
--
30
--
30
--
30
--
Reconnect time (T < 3S)
60
--
5
--
5
--
300
--
Reconnect time (normal)
60
--
30
--
30
--
300
--
Voltage high OFF (Fast)
264.5
0.08 sec
264.5
0.2 sec
255.3
0.2 sec
242
0.2 sec
Voltage high ON (Fast)
250.7
--
259.5
--
251.3
--
237
--
Voltage low OFF (Fast)
184.0
0.08 sec
184
0.2 sec
184
0.2 sec
187
0.2 sec
Voltage low ON (Fast)
197.8
--
189
--
189
--
192
--
Frequency high OFF (Hz)
51.50
0.08 sec
50.2
0.2 sec
50.2
0.2 sec
60.3
0.2 sec
Frequency high ON (Hz)
50.05
--
50.15
--
50.15
--
60.1
--
Frequency low OFF (Hz)
47.50
0.08 sec
47.5
0.2 sec
46
0.2 sec
59.7
0.2 sec
Frequency low ON (Hz)
47.55
--
47.55
--
46.1
--
59.9
--
Voltage high OFF (Slow)
253.0
600 sec
253
600 sec
253
600 sec
242
600 sec
Voltage high ON (Slow)
250.0
--
250
--
250
--
239
--
Voltage low OFF (Slow)
--
--
--
--
--
--
--
--
Voltage low ON (Slow)
--
--
--
--
--
--
--
--
DC Injection (mA)
--
--
1000
0.2 sec
1000
0.2 sec
0.45%
0.2 sec
Ground Current (mA)
300
0.3 sec
300
0.3 sec
300
0.3 sec
300
0.3 sec
Insulation
Yes
5 sec
Yes
5 sec
Yes
5 sec
Yes
5 sec
Islanding
Yes
Yes
Yes
Yes
Islanding Factor
100
100
100
100
Active Power
Yes
--
--
--
Reactive Power
Yes
--
--
--
Frequency de-rating
Yes
--
--
--
Power slow-up
Yes
--
--
--
Summary of Contents for CPSPV2000ETL-IN SLV