CyberPower 10K On-Line series User Manual Download Page 33

6.3.2 Parallel installation and operation

How to install a new parallel UPS system:

1)

2)

3)

4)

5)

6)

7)
8)
9)

Before installing a new parallel UPS system, user need to

prepare the input and output wires, the output breaker, and the
parallel cable.

Users need to use a standard 25-pin communication cable,

which should have 25 cores, corresponding stitches and shield,
as the UPS parallel cable. The length of the parallel cable is
appropriate to be less than 3m. And there is one standard
parallel cable in the accessories of every UPS.

Remove the cover plate of the parallel port on the UPS,

connect each UPS one by one with the parallel cable, and
re-screw the Parallel port cover which is supplied in the
accessories.

Strictly follow the chapter of 4, the wiring requirement of single

UPS to perform the wiring of each UPS.

Connect the output wires of each UPS to an output breaker

panel.

Disconnect the Jumper on J1 and J2 of the terminal block

first, and connect each output breaker to a main output breaker
and then to the loads.

Each UPS need an independent battery pack.
Please refer to the wiring diagram in the following diagram.
The distance between the UPSs in parallel and the breaker

panel is required to be less than 20 meters. The difference
between the wires of input and output of the UPSs is required to
be less than 20%.

30

Summary of Contents for 10K On-Line series

Page 1: ...User s Manual...

Page 2: ...9 4 Installation 11 4 1 Moving to The Installation Site 11 4 2 Unpacking and Inspection 11 4 3 Input and Output Power Wires and Protective Earth Ground Installation 12 4 4 Operating Procedure for Con...

Page 3: ...7 3 Trouble Shooting In Else Cases 38 8 Battery Maintenance 39 9 Communication Port 40 9 1 USB Interface 40 9 2 Dry contact Interface optional 40 9 3 RS 232 Interface 40 9 4 Intelligent slot 40...

Page 4: ...ed to direct sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step...

Page 5: ...source batteries In order to fully disconnect the UPS first turn the input breaker in the OFF position then disconnect the mains lead Indiscriminate operation of switches may cause output loss or dam...

Page 6: ...ips and handles When changing batteries replace with the same quantity and the same type of batteries Do not attempt to dispose of batteries by burning them It could cause explosion The UPS may be con...

Page 7: ...40 2 Category C3 EMS Level 3 Level 3 Level 4 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 11 Low Frequency Signals IEC EN 61000 2 2 Warning This is a pro...

Page 8: ...miliarize yourself with them and understand their meaning 5 Symbol and Explanation Symbol Explanation Symbol Explanation Alert you to pay special attention Caution of high voltage Alternating current...

Page 9: ...maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model...

Page 10: ...to the worst mains input condition Extra wide input voltage frequency range and waveform avoid excessive dissipating limited battery energy Internal charger could be up to 4Amps to decrease rechargin...

Page 11: ...Storage temperature 15 C to 50 C BATTERIES Model No 6K 8K 10K Internal BAT number and type 20 12V 28W 20 12V 28W 20 12V 34W BAT pack 28A 37 4A 47A The load capacity would be derated to 90 automaticall...

Page 12: ...708 x 550 70 6KXL 260 x 708 x 550 25 8K 260 x 708 x 550 86 8KXL 260 x 708 x 550 28 10K 260 x 708 x 550 86 10KXL 260 x 708 x 550 28 Model No 100 Load 6K 5 8K 5 10K 4 3 4 Typical Backup Time Typical val...

Page 13: ...PO Port Dry contact optional Intelligent Slot Fan Parallel Port Maintenance Switch Input Breaker Terminal Block 6K XL 10K XL Fig 3 1 Back View of 6K XL 10K XL The back view of 8K XL models are same as...

Page 14: ...allet jack or a truck before unpacking the UPS 4 2Unpacking and Inspection 1 At the installation site the utmost care shall be taken when removing the packaging in order to avoid damaging the equipmen...

Page 15: ...ler immediately if there is any damage or lacking of some parts 4 3 Input and Output Power Wires and Protective Earth Ground Installation 4 3 1 Notes for installation 1 The UPS must be installed in a...

Page 16: ...ry Cabinet Breaker in Positive Pole Negative pole Neutral Pole 32A 240VDC 50A 240VDC Torque for fixing above terminals 3 95 4 97Nm 35 44 1b in 4 3 2 Installation For safety please cut off the mains po...

Page 17: ...ommended to select the UL1015 8AWG 6mm 2 or other insulated wire which complies with AWG Standard for the UPS input and output wirings 5 For 8 10KVA UPS it is recommended to select the UL1015 6AWG 10m...

Page 18: ...only for XL model 10 Install an output breaker between the output terminal of UPS and the load and the breaker should with leakage current protective function if necessary 11 Turn off all the loads fi...

Page 19: ...e should be strictly followed For 6KVA select the UL1015 8AWG 6mm 2 respectively or other insulated wire which complies with AWG Standard for the UPS battery wirings For 8 10KVA select the UL1015 6AWG...

Page 20: ...supplies is when the emergency occurs such as the failure of load the UPS can cut off the output at once by operating the EPO port manually 4 5 2 The connection Normally the EPO connector is closed wi...

Page 21: ...on more than 1S to turn on Turn off When the unit has been turned on press this button more than 3S to turn off 5 Operation 5 1 Display Panel The UPS has a five button dot matrix LCD with white text a...

Page 22: ...n to previous menu Up Press this button more than 200mS to move the focus to the up menu Down Press this button for more than 200mS to move the focus to the down menu UPS state Normal LED Green Batter...

Page 23: ...nd settings through the front panel display During powering on the LCD would display the CyberPower logo for several seconds and then enter to the default page which shows the UPS status summary On th...

Page 24: ...continuously for more than 1 second the buzzer will beep for 1s UPS starts to turn on 4 A few seconds later the UPS turns into Line mode If the mains power is abnormal the UPS will transfer to Battery...

Page 25: ...down and no voltage is available from the UPS output 5 3 LCD Operation Except the default UPS status summary screen the user could get more useful information about UPS current status old events which...

Page 26: ...Fig 5 2 status menu 23...

Page 27: ...s Fault Clear all events Clear all faults Event 0001 12 00 00 Utility abnormal 1 10 Alarm 0002 12 00 00 Overload 1 10 Fault 0003 12 00 00 Over tempearture 1 5 Clear all events Yes No Clear all faults...

Page 28: ...he same time Clear EPO status once EPO status is enabled the UPS output would be cut off To recover to normal status first EPO connector should be closed and enter this menu to clear EPO status then U...

Page 29: ...ome settings would change the specification and some settings would enable or disable some functions The unsuitable option set by user may result in potential failures or protecting function loss even...

Page 30: ...Short circuit clearance enabled disabled disabled Power strategy normal Rated output voltage 208 220 230 240V 230V Output frequency autosensing 50 60Hz autosensing Bypass voltage low range 10 15 20 15...

Page 31: ...uld be gained in ECO mode Once the mains power is loss or abnormal the UPS would transfer to Line mode or Battery mode and the load is supplied continuously The great virtue is overall high efficiency...

Page 32: ...e enabled through the LCD setting in Bypass mode Enter the power strategy setting menu by following chapter of 5 3 4 6 3 Parallel Function 6 3 1 Brief introduction of the redundancy N X is currently t...

Page 33: ...port on the UPS connect each UPS one by one with the parallel cable and re screw the Parallel port cover which is supplied in the accessories Strictly follow the chapter of 4 the wiring requirement o...

Page 34: ...Fig 6 1 Input and output Terminal Block wiring diagram 31...

Page 35: ...hem is less than 1V If the difference is more than 1V check the wiring 11 Press the button of one UPS each UPS would start to turn on all the UPSs would transfer to the INV mode together Measure the o...

Page 36: ...ce switch of each UPS from UPS to BPS Set the main maintenance switch or static switch from UPS to BPS switch off the main output breaker and the main input breaker the UPSs would shut down Ensure the...

Page 37: ...the wanted UPS and reinstall the new UPS parallel system by following step 1 to 9 of last chapter install a new parallel UPS system If the removed UPS or the remained UPS will be used in a stand alon...

Page 38: ...nnected to the UPS Check the battery breaker is turn on Battery low Battery voltage is low When audible alarm sounding empty Output Overload Overload Check the loads and remove some non critical loads...

Page 39: ...fer The battery packs of some UPSs are disconnected Check if all the battery pack is connected Para Line Differ The mains input of some UPSs is disconnected Check the building wiring and input cable C...

Page 40: ...dealer Bus Under Voltage UPS internal fault Consult dealer Bus Unbalance UPS internal fault Consult dealer Bus short UPS internal fault Consult dealer Bus Softstart Fail UPS internal fault Consult de...

Page 41: ...he building wiring and input cable Check if the input breaker is closed Emergency supply period shorter than nominal value Batteries not fully charged batteries defect 12 hours and then check capacity...

Page 42: ...ging and over discharging The UPS should be charged once every 4 to 6 months if it has not been used for a long time In the regions of hot climates the battery should be charged and discharged every 2...

Page 43: ...contact interface Please contact your local distributor for details 9 3 RS 232 Interface The RS 232 port is available for UPS monitoring control and firmware updates 9 4 Intelligent slot This series i...

Reviews: