
8) Connect other input and output wires to the corresponding input
and output terminals according to the following diagram.
9) It is requested to use the accessorial terminal splices which can
be compacted on the wires tightly, to ensure the connection
between the wires and the terminal block is reliable.
Fig. 4-7 Input and output Terminal Block wiring diagram
Notes:
1) If the UPS is used in single mode, J1 and J2 must be
connected. If the UPS is used in parallel mode, the Jumper
between J1 and J2 must be removed.
2) /- connection is only for “XL” model.
10) Install an output breaker between the output terminal of UPS
and the load, and the breaker should with leakage current
protective function if necessary.
11) Turn off all the loads first before connecting the load with the
UPS, then perform the connection and finally turn on the loads
one by one.
12) After completing the installation, check all the wires is
connected correctly and tightly.
13) Suggest charging the batteries for 8 hours before use. After
installation, turn on the mains power switch and turn the input
breaker in the “ON” position, the UPS will charge the batteries
automatically. It can also use the UPS immediately without
charging the batteries, but the backup time may be less than the
standard value.
15
Summary of Contents for 10K On-Line series
Page 1: ...User s Manual...
Page 26: ...Fig 5 2 status menu 23...
Page 34: ...Fig 6 1 Input and output Terminal Block wiring diagram 31...