5.3.3 The control menu
By pressing
on the menu of “Control”, the display would enter
the next control menu screen.
1)
2)
3)
4)
Single UPS turn off: is one command to turn off one UPS which
is operated currently in a parallel system, and other UPSs
continue working to supply the load in the parallel system.
UPS battery test: is one command to control all UPS in
a parallel system to do the battery test at the same time.
Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be closed, and enter this menu to clear EPO
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
Reset fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
to reset error status, then UPS would stop alarm and recover to
Bypass mode. And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.