18
USING THE UPS SYSTEM
INDEX SET UP ITEMS
AVAILABLE SETTINGS
DEFAULT
SETTING
01
Output Voltage
=[208V] [220V] [230V] [240V]
Sets UPS output voltage
230V
02
Sync Freq
Window
Range= [+/- 1%] [+/- 2%] [+/-3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%]
Sets output synchronization frequency range
If input line frequency is outside this range, the UPS
will lock in at the nominal frequency.
+/- 5%
03
Bypass V
Window
Range= [+10%][+15%] / [-10%][-15%][-20%]
Sets Bypass Voltage range
+10%/-15%
04
Bypass
Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Bypass Condition:
The default setting [Check Freq/Volt] means the UPS
will check the following specifications (1) and (2) when
UPS has fault and needs transfer to Bypass.
The setting [Check Volt Only] means the UPS will check
the following specification (1) when UPS has fault and
needs transfer to Bypass.
(1) Bypass voltage is inside the range of "Bypass V
Window".
(2) Bypass frequency is inside the range of "Sync
Freq Range".
The setting [No Bypass] means the UPS is forbidden to
transfer to Bypass when UPS has fault.
Check
Freq/Volt
(2) SET UP
There are 32 UPS items that can be Set Up by the user.
1. Press the “UP” and “DOWN” buttons to select the “SETUP” ICON.
2. Press the “ENTER” button to enter the “SETUP” function.
3. Press the “UP” and “DOWN” buttons to scroll to the “SETUP” option.
4. When selecting the submenu item, the code number will be exhibited.
5. Press the “ENTER” button to select the “SETUP” submenu items shown in the table below.
6. Press the “UP” and “DOWN” buttons to scroll through the different parameters.
7. Press the “ENTER” button to select the parameter you want to set up.
8. You may be prompted “Save” to save the selection, if so press the “ENTER” button to save
the setting. Some options are saved and started automatically. (See the following table and
screen for additional details.)
9. Press the “ESC” to cancel or return to the previous SET UP menu.