Small Oval Remote Burner – Perspective View of Back:
NOTE:
Gas inlet runs through the back hole of the bowl
Commissioning the Fire
TEST THE GAS PRESSURE. Turn the fire on full; attach a manometer
to the inlet test point and ensure there is a pressure of 20mbar (+/-
1mbar) for natural gas appliances or 37mb for propane appliances.
Now turn on all the other gas appliances in the house and re check
pressure. The pressure must still be in the tolerance of +/- 1mb.
Now turn off all the other gas appliances and turn the fire down to
pilot only, the pressure must still be in the tolerance of +/- 1mbar. If
it is not, TRANSCO, BORD GAIS or the propane supplier must be called
to adjust the governor to the house before the fire can be
commissioned further.
Brief the customer on the operation of the appliance and give them
the instructions. The customer must be told of the need for regular
servicing of the appliance, this will be at least once a year, and be
made aware that no rubbish is to be thrown onto the fire bed.
The
customer must also be aware that purpose provided ventilation
should be checked regularly.