background image

 

M869-GB-2_Letter

 

5 / 10 

mini NEB US

 

3.4. Hydraulic 

connections 

Pic

Pic

Pic

Pic. . . . 3.4

3.4

3.4

3.4....1

11

1    ––––    Hydraulic connections

Hydraulic connections

Hydraulic connections

Hydraulic connections    

The installation of the 

machines requires the 
connections to the hoses 

for water feeding and 

discharge. The hoses, 

included with the 

humidifier, must be 

fitted as described 

below.

 

The water supply 

hose A 

has a threaded 

bush G ¾ on both ends.

 

Connect the L-shaped 

end to the solenoid 
valve of the MININEB, 

and the other end (the 

straight one) directly to 

a tap (B) or an 

extention. It’s suggested 

to connect a mechanical 

water filter (C) 
downstream the tap B. 

Concerning the water 

discharge, use the hose D supplied or, 

if a longer hose is needed, make sure it has an 

internal diameter of 

3/8”. The hose must be installed as represented in Pic. 3.4.1 with a minimal gradient of 10°, to guarantee 
the correct water discharge. An eventual siphon E must be on the main discharge and not on the hose 

connected to the machine. 

To guarantee a regular and efficient water discharge, carefully check that the discharge hose is fitted with 
a gradient and stright, without elbows or bottlenecks of any kind. 

3.5. Wall 

installation 

 

Pic

Pic

Pic

Pic. . . . 3.5

3.5

3.5

3.5....1

11

1    ––––    W

W

W

Wall mounting bracket

all mounting bracket

all mounting bracket

all mounting bracket    

Use the supplied metal bracket shown on 
Pic. 3.5.1 with screws to install the 

machine to a wall. The special bracket 

can be used as a template to mark the 

holes to be made on the wall, as in Pic. 

3.5.2. 

 

Observe the minimal distances 

written at the Par. 3.2; 

 

Check that the extremities of the 

bracket are perfectly horizontal 

before holing. 

 

Check that the wall where the 

machine will be installed is able to 

sustain the weight in operative 

conditions. 

Pic

Pic

Pic

Pic. . . . 3.5

3.5

3.5

3.5....2

22

2    –––– Holes 

 Holes 

 Holes 

 Holes on the wall

on the wall

on the wall

on the wall    

 

Summary of Contents for MININEB

Page 1: ...Adiabatic humidifier ...

Page 2: ......

Page 3: ...ure 14 5 psi 145 psi Water Supply Tank Capacity Water Supply Tank Capacity Water Supply Tank Capacity Water Supply Tank Capacity 0 12 lbs Working Temperatures Working Temperatures Working Temperatures Working Temperatures 33 4 F 95 F Working Relative Humidity Working Relative Humidity Working Relative Humidity Working Relative Humidity 0 100 R H non condensing Degree of protection Degree of protec...

Page 4: ......

Page 5: ...Pic 3 2 2 Pic 3 2 3 in horizontal position with the air filter directioned below leaving a correct space from the ground Any other positioning compromizes the correct performance of the machine 3 2 1 Minimal distances Pic Pic Pic Pic 3 2 3 2 3 2 3 2 1 1 1 1 Pic Pic Pic Pic 3 2 3 2 3 2 3 2 2 2 2 2 Pic Pic Pic Pic 3 2 3 2 3 2 3 2 3 3 3 3 A A A A B B B B C C C C D D D D minima minima minima minimal l...

Page 6: ...on both power supply lines Pic Pic Pic Pic 3 3 3 3 3 3 3 3 1 1 1 1 Wiring diagra Wiring diagra Wiring diagra Wiring diagram m m m 3 3 2 Cabling Referring to Pic 3 3 2 Remove the cover of the electrical connection box located on the rear of the machine unscrewing screws V Pass the electrical power supply cable through the cable holder P Take off the terminal board M from the box Connect phase neutr...

Page 7: ... gradient of 10 to guarantee the correct water discharge An eventual siphon E must be on the main discharge and not on the hose connected to the machine To guarantee a regular and efficient water discharge carefully check that the discharge hose is fitted with a gradient and stright without elbows or bottlenecks of any kind 3 5 Wall installation Pic Pic Pic Pic 3 5 3 5 3 5 3 5 1 1 1 1 W W W Wall m...

Page 8: ...to the bracket as represented in Pic 3 5 3 Screw the last two screws and finally fasten all the four screws Check the installation solidity 3 6 Hang up installation The Hang up installation can be made using the supplied special shaped hooks Pic 3 6 1 It is necessary to prearrange three support chains where to hang up the machine The chains must be as vertical as possible and attached to connectio...

Page 9: ...ontained in the machine will fall down on the water basin and trigger the siphon that will discharge it It s suggested to close the water feed tap Between the switch off and the successive start up of the humidifier there must be a time delay of at least 30 seconds to allow the siphon to discharge the basin completely If this does not happen the siphon remains triggered and the water will be conti...

Page 10: ...of the machine Referring to Pic 5 2 1 Disassemble the filter unscrewing the two V screws that keep it in place Remove the net R and the air filter F Clean the air filter F with a vacuum cleaner or by rinsing it into soaped water Dry it without wringing Reassemble all the pieces carefully checking that the filter is correctly positioned and the net tightened with the screws Never start the humidifi...

Page 11: ...d bush A of the water supply hose the filter is located inside the threaded bush E of the solenoid valve If cleaning becomes too frequent it is advisable to install a cartridge filter on the machine water supply line see paragraph 3 4 Hydraulic connections Pic Pic Pic Pic 5 4 5 4 5 4 5 4 1 1 1 1 Solenoid valve Solenoid valve Solenoid valve Solenoid valve 6 Storage 6 1 General notes Store the machi...

Page 12: ...es out from the air outlet but not nebulized water POSSIBILE CAUSES SOLUTIONS Water does not arrive to the basin Check that the water supply tap is opened Check that the water feed solenoid valve filter is not obstructed and that the hoses are correctly fitted and unobstructed Finally check that the floating switch inside the basin is free to move correctly The fan cone extremity is obstructed Cle...