Part No. 4801-3030 Rev. 1-15
Page
18
of
22
Super Saver XL-240 Heater
Table 1
Minor Loss Equivalents
Fitting
2" (5.08 cm) IPS Or Smaller
2” (5.08 cm) IPS To 4” (10.16 cm) IPS
Feet per fitting
Meters per fitting
Feet per fitting
Meters per fitting
45
Elbow
1
1
5
2
90
Elbow
2
2
10
3
Tee
4
4
20
6
Gate Valve
1
1
3
1
Angle Valve
9
9
60
18
Swing Valve
5
5
30
9
-
Table 2. Maximum Capacity Of Pipe In Thousands Of BTU per Hour
Nominal
Internal
Natural Gas (Methane) @ Pressure Drop Of 0.5 in w.c. (0.2 mbar)
Iron Pipe
Diameter,
Values listed are for 0.6 sp.gr. based on Heat Of Combustion of 1000 BTU/cu .ft
Size,
(IPS)
Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)
Inch*
Inch*
10
20
30
40
50
60
70
80
90
100
150
200
250
300
1/2
.622
175
120
97
82
73
66
61
57
53
50
40
35
29
25
3/4
.824
360
250
200
170
151
138
125
118
110
103
84
72
59
53
1
1.049
680
465
375
320
285
260
240
220
205
195
160
135
109
100
1-1/4
1.380
1400
950
770
660
580
530
490
460
430
400
325
280
219
206
1-1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
500
430
325
309
2
2.067
3950
2750
2200
1900
1680
1520
1400
1300
1220
1150
950
800
614
596
2-1/2
2.469
6300
4350
3520
3000
2650
2400
2250
2050
1950
1850
1
1500
0
1280
966
950
3
3.068
11000
7700
6250
5300
4750
4300
3900
3700
3450
3250
2650
6
2280
1855
1680
4
4.026
23000
15800
12800
10900
9700
8800
8100
7500
7200
6700
5500
1
4600
3783
3432
Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3
* 1 inch = 25.4 mm
Pipe Sizes Determined For Diagram
Pipe Section
Max Gas Capacity Value Determined From Table 2
Pipe Size Determined From Table 2
BTUH
kWh
inches
mm
a-b
280,000
82
1-1/4 in
31.8
b-c
135,000
40
1 in
25.4
b-d
72,000
21
¾ in
19.1
b-f
72,000
21
¾ in.
19.1
c-e
72,000
21
¾ in.
19.1
c-g
72,000
21
¾ in .
19.1
Table 3. Maximum Capacity Of Pipe In Thousands Of BTU per Hour
Nominal
Internal
Liquid Propane (LP) @ Pressure Drop Of 0.5 in w.c.
Iron Pipe
Diameter,
Values listed are for 1.6 sp.gr. based on Heat Of Combustion of 2500 BTU/cu .ft
Size,
(IPS)
Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)
Inch*
Inch*
10
20
30
40
50
60
70
80
90
100
125
150
1/2
.622
275
189
152
129
114
103
96
89
83
78
69
63
3/4
.824
567
393
315
267
237
217
196
185
173
162
146
132
1
1.049
1071
732
590
504
448
109
378
346
322
307
275
252
1-1/4
1.380
2205
1496
1212
1039
913
834
771
724
677
630
567
511
1-1/2
1.610
3307
2299
1858
1559
1417
1275
1181
1086
1023
976
866
787
2
2.067
6221
4331
3465
2992
2646
2394
2205
2047
1921
1811
1606
1496
Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3.
* 1 inch = 25.4 mm
IMPORTANT
Tables 2 and 3 are based on values given in the Gas Engineers Handbook and are intended as a guide only.
Consult your gas supplier for gas capacity and pipe size information for your particular piping system.